- Description
The Schneider Electric ATV310HU55N4E is a variable frequency drive from the Easy Altivar 310 range, built for simple machines on a 380-460 V three-phase supply. In heavy duty it delivers 12.6 A continuous output for 5.5 kW motors (16.0 A / 7.5 kW in normal duty). It includes an integrated Modbus RS485 port, sensorless vector control, and IP20 protection with an integrated cooling fan.
Technical Specifications
| Reference | ATV310HU55N4E |
| Brand | Schneider Electric |
| Range | Easy Altivar 310 |
| Product Type | Variable speed drive |
| Phase | Three phase |
| Rated Supply Voltage (Us) | 380-460 V AC |
| Motor Power, Heavy Duty | 5.5 kW |
| Motor Power, Normal Duty | 7.5 kW |
| Continuous Output Current, Heavy Duty | 12.6 A |
| Continuous Output Current, Normal Duty | 16.0 A |
| Maximum Transient Current | 18.9 A for 60 s (heavy duty) |
| Output Frequency Range | 0.5-400 Hz |
| Switching Frequency | 2-12 kHz adjustable, 4 kHz nominal |
| Motor Control Profile | V/f, energy-saving quadratic U/f, sensorless vector control (SVC) |
| Communication Port | Modbus, RJ45, 2-wire RS 485 |
| Analogue I/O | 1 analogue input, 1 analogue output |
| Discrete I/O | 4 discrete inputs, 2 discrete outputs (1 relay) |
| IP Degree of Protection | IP20 (IP4X top) |
| Pollution Degree | 2 (IEC 61800-5-1) |
| Ambient Operating Temperature | -10 to 55 degC (without derating) |
| Dimensions (H x W x D) | 184 x 140 x 151 mm |
| Net Weight | 1.8 kg |
| Noise Level | 50 dB |
Certifications & Standards
- CE
- EAC
- KC
- IEC 61800-3
Selection Notes
The heavy-duty rating (12.6 A continuous, 5.5 kW) suits variable-torque loads such as pumps and fans, where overload margin matters less than continuous current headroom. The normal-duty rating (16.0 A, 7.5 kW) on the same frame suits constant-torque loads that draw more current continuously. Sensorless vector control is available alongside standard V/f control for applications needing better torque at low speed than open-loop V/f alone provides. The drive ships without an EMC filter, so external filtering is needed where EN 61800-3 conducted-emission limits apply.