- Home
- Schneider Altistart Soft Starters
- Schneider Electric ATS490D32Y Altivar ATS490 32 A 208-690V 3-Phase 15 kW Soft Starter Schneider Electric ATS490D32Y Altivar ATS490 32 A 208-690V 3-Phase 15 kW Soft Starter
Schneider Electric ATS490D32Y Altivar ATS490 32 A 208-690V 3-Phase 15 kW Soft Starter
Schneider Electric ATS490D32Y Altivar ATS490 32 A 208-690V 3-Phase 15 kW Soft Starter
Get Quote
- Description
The Schneider Electric ATS490D32Y is a soft starter from the Altivar Soft Starter ATS490 range, built to ramp asynchronous motors smoothly from a 208-690 V AC supply. In normal duty it carries 32 A continuous (22 A in heavy duty) and drives up to 15 kW at 400 V. It integrates Safe Torque Off, native Modbus TCP/EtherNet/IP, and IP20 protection for enclosure mounting.
Technical Specifications
| Reference | ATS490D32Y |
| GTIN | 3606486948774 |
| Brand | Schneider Electric |
| Range | Altivar Soft Starter ATS490 |
| Product Type | Soft starter |
| Phase | 3 phase |
| Rated Operational Current, Normal Duty (Ie) | 32 A |
| Rated Operational Current, Heavy Duty | 22 A |
| Supply Voltage (Ue) | 208-690 V AC |
| Control Circuit Voltage (Us) | 110-230 V AC |
| Control Circuit Voltage (Uc, logic) | 24 V DC |
| Motor Power at 400 V, Normal Duty | 15 kW |
| Motor Power at 400 V, Heavy Duty | 11 kW |
| IP Degree of Protection | IP20 |
| Communication Protocol | Modbus serial, Modbus TCP/EtherNet/IP |
| Safe Torque Off (STO) | SIL 1 (IEC 61508), PL c / Category 2 (ISO 13849) |
| Overload Current Profile | 400% Ie for 13 s |
| Relay Outputs | 3, 2 A / 250 V AC (AC-15) |
| Rated Insulation Voltage (Ui) | 690 V |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Ambient Operating Temperature | -25 to 40 degC (without derating) |
| Dimensions (H x W x D) | 289 x 160 x 234 mm |
| Net Weight | 6 kg |
Certifications & Standards
- CE
- cULus
- UKCA
- RCM
- CCC
- DNV
- ATEX
- EAC
- KC
- EN/IEC 60947-4-2
- UL 60947-4-2
- IEC 60664-1
Selection Notes
The 32 A normal-duty rating covers motors up to 15 kW at 400 V; where the load runs a more demanding duty cycle, the heavy-duty curve drops to 22 A for motors up to 11 kW. The 400% Ie for 13 s overload profile sets how long the starter tolerates a stalled or jammed load before tripping, relevant when sizing against pump or conveyor startup torque. The integrated Safe Torque Off input meets SIL 1 / PL c without an external safety contactor on the motor branch.
Applications
The ATS490 range targets pumps, fans, compressors, conveyors, mixers, cutters, grinders, and crushers where a controlled, torque-limited start reduces mechanical and electrical stress at startup.