- Description
The Schneider Electric ATS430D17S6 is a 3-phase Altivar Soft Starter ATS430 rated for 17A continuous operation on a 208-600V AC supply. It drives asynchronous motors up to 9kW depending on line voltage, using torque control with 99.5% efficiency and an internal bypass to limit heat dissipation once the motor is running at speed.
Technical Specifications
| Reference | ATS430D17S6 |
| Brand | Schneider Electric |
| Range | Altivar Soft Starter ATS430 |
| GTIN | 3606486948606 |
| Product Type | Soft starter |
| Phase | 3 phase |
| Rated operational current (Ie) | 17 A at 40 °C, normal duty |
| Supply voltage (Ue) | 208...600 V AC (-15...+10%) |
| Control circuit voltage (Us) | 110...230 V AC 50-60 Hz (-15...+10%) |
| Motor power | 4 kW at 230 V | 7.5 kW at 400 V | 7.5 kW at 440 V | 9 kW at 500 V | 9 kW at 525 V |
| IP Degree of Protection | IP20 |
| Torque control | Yes |
| Overload current | 400% Ie for 13 s |
| Discrete inputs | 4 (STOP, RUN, DI3, DI4) |
| Relay outputs | 2 (2 A / 250 V AC or 2 A / 30 V DC) |
| Analogue I/O | 1 input (PTC probe), 1 output (0-20/4-20 mA or 0-10 V) |
| Communication | Modbus serial (RJ45 or open-style terminals) |
| Rated insulation voltage (Ui) | 600 V |
| Rated impulse withstand voltage (Uimp) | 6 kV |
| Internal bypass | Yes |
| Operating position | Vertical ± 10° |
| Dimensions (H x W x D) | 273 x 130 x 169 mm |
| Net weight | 2.90 kg |
Certifications & Standards
- cULus
- CE
- UKCA
- CCC
- RCM
- EAC
- KC
- EN/IEC 60947-4-2
- UL 60947-4-2
- IEC 60664-1
Selection Notes
The 17A rating sizes the ATS430D17S6 for motors from 4kW at 230V up to 9kW at 500-525V, so match the drive to the actual line voltage rather than the current figure alone. The 400% Ie for 13s overload rating and internal bypass keep dissipation low once the motor reaches full speed, which matters most on frequent-cycling loads such as pumps, fans, compressors, conveyors, and mixers. Pick the next size up in the ATS430 range when the driven load's starting torque or duty cycle exceeds the 17A frame's 13-second overload window; pick the size below it when the motor's full-load current sits well under 17A, since an oversized starter loses current-limiting resolution.