Siemens 6EP4438-7FB00-3DX0 is a SITOP SEL1200 8-channel selectivity module that splits a single 24 V DC, 60 A supply into eight individually protected 2-10 A outputs, each adjustable via potentiometer. It isolates a fault on one branch circuit without tripping the upstream supply, using a three-color LED per output and a floating signal contact for remote diagnostics.
Technical Specifications
| SKU | 6EP4438-7FB00-3DX0 |
| Brand | Siemens |
| Series | SITOP SEL1200 |
| Product Designation | SEL1200 |
| Input Voltage (DC) | 24 V DC (20.4-30 V range) |
| Input Current (rated) | 60 A |
| Number of Outputs | 8 |
| Output Current per Channel | 10 A rated (2-10 A adjustable threshold) |
| Response Delay | 5 s max. |
| Efficiency | 98% |
| Power Loss | 18 W typ. at rated output |
| Switch-Off Characteristic | 1.0x to 2.0x set value thresholds, 5 s to 30 ms trip time |
| Remote Reset | Non-isolated 24 V input (signal level greater than 15 V) |
| Protection Class | IP20, Class III |
| MTBF (40 C) | 925,000 h |
| Dimensions (W x H x D) | 45 x 135 x 125 mm |
| Net Weight | 0.3 kg |
Certifications & Standards
- CE
- UL 2367
- cULus (UL 508)
- UKCA
- EAC
- CB
- DNV
- EPD
Selection Notes
Each of the 8 outputs trips independently on overcurrent (Iout greater than 2.0x set value clears in about 30 ms; Iout greater than 1.0x set value clears in about 5 s), so a shorted branch drops only that channel instead of pulling down the shared 24 V bus - pick this over a single large-frame breaker when a machine has multiple independent 24 V DC sub-circuits that must fail separately. The per-channel threshold is field-adjustable 2-10 A via potentiometer, so the same module covers mixed loads (sensors on 2 A, valve banks on 8-10 A) without needing separate fixed-current modules. A DIN-rail width of only 45 mm keeps cabinet footprint small for 8 protected outputs.
Applications
Used downstream of a bulk 24 V DC power supply to give each machine zone, sensor group, or actuator bank its own selectively protected output, so a single shorted branch does not shut down the whole control cabinet.