- Description
The Siemens 6EP4347-7RB00-0AX0 is a SITOP RED1200 redundancy module that decouples two independent 24/48 V DC power supplies, each rated up to 20 A, into a single combined 40 A output for load-sharing or 1+1 redundant operation. It reaches 97.5% efficiency with only 25 W power loss at full rated output and mounts on a 35 mm DIN rail.
Technical Specifications
| SKU | 6EP4347-7RB00-0AX0 |
| Brand | Siemens |
| Series | SITOP RED1200 |
| Product Type Designation | RED1200 |
| Input Voltage, DC | 12...48 V (10...58 V range) |
| Output Voltage, Rated | 24V DC (12...48V per input) |
| Output Current, Rated | 40 A |
| Efficiency | 97.5% |
| Power Loss, Typ. | 25 W |
| No-Load Power Loss, Max. | 0.1 W |
| MTBF at 40 degrees C | 6,100,000 h |
| Enclosure Dimensions (WxHxD) | 45 x 135 x 125 mm |
| Protection Class | IP20 |
| Ambient Temperature, Operation | -40 to +70 degrees C |
| Net Weight | 0.51 kg |
Certifications & Standards
- CE
- EPD
Selection Notes
Feeding the module from two separate 24 V, or up to 48 V, supplies rated 20 A each lets either supply fail without interrupting the shared 40 A output bus - the redundancy sits at the power-supply level, so the two source units still need to be sized and protected independently. The wide 12-48 V DC input range covers both 24 V and 48 V DC distribution schemes on the same part number. At 97.5% efficiency and 25 W typical loss, cabinet heat load stays low even feeding a fully loaded 40 A bus continuously.
Applications
N+1 redundant 24 V or 48 V DC power distribution for control systems where a single power-supply failure must not interrupt PLC, I/O, or drive control power, such as process plants and continuous-operation machine control cabinets.