- Home
- Redundancy, Selectivity & DC Converter Modules
- Siemens 6EP4346-7RB00-0AX0 SITOP RED1200 24/48V 20A Redundancy Module Siemens 6EP4346-7RB00-0AX0 SITOP RED1200 24/48V 20A Redundancy Module
Siemens 6EP4346-7RB00-0AX0 SITOP RED1200 24/48V 20A Redundancy Module
Siemens 6EP4346-7RB00-0AX0 SITOP RED1200 24/48V 20A Redundancy Module
Get Quote
- Description
The Siemens 6EP4346-7RB00-0AX0 SITOP RED1200 is a redundancy module that decouples two SITOP power supplies, each up to 10 A, into a single 24/48 V DC output rated 20 A. It reaches 97.5% efficiency with only 0.1 W no-load loss, letting either input source fail without interrupting the downstream 24 V bus.
Technical Specifications
| SKU | 6EP4346-7RB00-0AX0 |
| Brand | Siemens |
| Series | SITOP RED1200 |
| Product type designation | RED1200 |
| Input voltage (DC) | 12-48 V (10-58 V range) |
| Output voltage (DC) | 24 V, formula: Vin - approx. 0.6 V |
| Output current, rated | 20 A |
| Efficiency | 97.5 % |
| Power loss at rated load, typ. | 12 W |
| No-load power loss, max. | 0.1 W |
| Degree of protection | IP20 |
| Operating temperature | -40…+70 °C |
| Connection method | Push-in terminals |
| Mounting | DIN rail EN 60715 35x7.5/15 |
| Enclosure dimensions (W×H×D) | 35 × 135 × 125 mm |
| Net weight | 0.47 kg |
Certifications & Standards
- CE
Selection Notes
A 20 A rated output paired with two inputs each capped at 10 A (per the module's two-supply decoupling spec) means this RED1200 unit is sized to redundantly back a load up to 20 A total — for a larger protected load, a higher-current SITOP power supply pair is needed upstream, not a different RED1200 variant. The output formula (Vin - approx. 0.6 V) indicates diode-based decoupling, so it needs no control power or configuration and drops directly into an existing 24 V DC bus between two supplies. The -40…+70 °C operating range and 97.5% efficiency keep self-heating low even in sealed enclosures.
Applications
Redundant 24 V power feeds for PLCs and safety-critical control loops, and dual-supply cabinet designs that need to eliminate a single point of failure.