- Home
- Power Quality, Metering & Power Supplies
- Siemens 6EP4133-0GA00-0AY0 SITOP BAT1600 24V 3.2Ah Lead-Acid DC UPS Module Siemens 6EP4133-0GA00-0AY0 SITOP BAT1600 24V 3.2Ah Lead-Acid DC UPS Module
Siemens 6EP4133-0GA00-0AY0 SITOP BAT1600 24V 3.2Ah Lead-Acid DC UPS Module
Siemens 6EP4133-0GA00-0AY0 SITOP BAT1600 24V 3.2Ah Lead-Acid DC UPS Module
Get Quote
- Description
The Siemens 6EP4133-0GA00-0AY0 SITOP BAT1600 is a 24 V DC, 3.2 Ah maintenance-free lead-acid battery module for the SITOP UPS1600 buffering system, rated 20 A continuous output with a 60 A / 30 ms peak. Charging draws up to 0.8 A, and a three-color LED reports buffer-ready, buffer-endangered, or buffer-not-possible status.
Technical Specifications
| SKU | 6EP4133-0GA00-0AY0 |
| Brand | Siemens |
| Series | SITOP UPS1600 |
| Product type designation | BAT1600 |
| Battery type | Maintenance-free lead-acid |
| Battery capacity | 3.2 Ah |
| Output voltage | 24 V DC |
| Output current, rated | 20 A |
| Peak current | 60 A (30 ms) |
| Charging current, max. | 0.8 A |
| End-of-charge voltage at 20°C | 27.3 V |
| Short-circuit protection | 25 A / 32 V Maxi flat fuse |
| Number of cells | 2 |
| Service life at 20°C, typ. | 4 years |
| Service life at 30°C, typ. | 2 years |
| Degree of protection | IP20 |
| Operating temperature | -15…+50 °C |
| Mounting | DIN rail EN 60715 35x15 or wall mount |
| Enclosure dimensions (W×H×D) | 89 × 156 × 169 mm |
| Net weight | 3.8 kg |
Certifications & Standards
- CE
- UKCA
- CB
- ABS
Selection Notes
3.2 Ah is the smallest capacity step in the BAT1600 module range, sized to buffer the lower output-current SITOP UPS1600 configurations rather than deliver long-runtime backup — pick a higher-Ah BAT1600 module where ride-through time matters more than footprint. The 4-year typical service life at 20°C drops to 1 year at 40°C, so cabinet ambient temperature directly sets the replacement interval and should be checked against the installation site. The built-in 25 A / 32 V fuse and three-color status LED let it report buffer health locally without a separate battery-monitoring module.
Applications
24 V buffering for PLCs and controllers behind a SITOP UPS1600, and short ride-through power-loss protection in machine control cabinets.