- Home
- Power Quality, Metering & Power Supplies
- Siemens 6EP3436-3SB00-0AX0 SITOP PSU4200 3AC 400/500V 24V/20A Power Supply Siemens 6EP3436-3SB00-0AX0 SITOP PSU4200 3AC 400/500V 24V/20A Power Supply
Siemens 6EP3436-3SB00-0AX0 SITOP PSU4200 3AC 400/500V 24V/20A Power Supply
Siemens 6EP3436-3SB00-0AX0 SITOP PSU4200 3AC 400/500V 24V/20A Power Supply
Get Quote
- Description
The Siemens 6EP3436-3SB00-0AX0 is a SITOP PSU4200 three-phase power supply converting 400/500 V AC input into a stabilized 24 V DC output rated at 20 A, adjustable from 24 to 28 V via potentiometer. It supplies 480 W typical active power at 91% efficiency and includes a DC-OK signal contact for status monitoring.
Technical Specifications
| SKU | 6EP3436-3SB00-0AX0 |
| Brand | Siemens |
| Series | SITOP PSU4200 |
| Product Type Designation | PSU4200 |
| Input | 3-phase AC, 400/500 V (rated range 320-550 V) |
| Line Frequency | 50/60 Hz |
| Output Voltage | 24 V DC, adjustable 24-28 V |
| Output Current | 20 A (range 0-20 A, derating 2%/K above 55 degC) |
| Output Power | 480 W typical |
| Efficiency | 91% |
| Residual Ripple | Max 150 mV |
| Inrush Current Limit | Max 36 A |
| Short-Circuit Protection | Constant current characteristic, typical 23.4 A |
| Signal Output | DC OK contact, 5 mA signal load capacity |
| Galvanic Isolation | Yes, SELV / ES1 (IEC 62368-1) |
| Protection Class | IP20 |
| Ambient Temperature (Operation) | -25 ... +70 degC |
| Dimensions (W x H x D) | 95 x 135 x 150 mm |
| Net Weight | 1.66 kg |
| Connection Method | Push-in terminals |
| MTBF at 40 degC | 815,000 h |
Certifications & Standards
- CE
- UKCA
- EAC
- RCM
- CB
- EPD
Selection Notes
The 20 A / 480 W rating scales this PSU4200 for panel-wide 24 V distribution, well above the lower-current SITOP families in this range - pick it when total connected load across multiple DIN-rail devices exceeds what a compact supply can carry. Direct 400/500 V three-phase input removes the need for a separate step-down transformer in 400 V industrial mains, and the integrated DC-OK signal contact allows the PLC to detect an output fault without a separate voltage-monitoring relay. Two units can be operated in parallel to increase available power.
Applications
Suited to control cabinet 24 V bus supply on three-phase 400/500 V industrial installations, multi-drive panels, and applications needing a hardware DC-OK signal for PLC-level power monitoring.