The Siemens SITOP select 6EP1961-2BA00 is a 4-channel diagnostics selectivity module that takes a 24 V DC/40 A input and distributes it across four outputs rated 10 A each, with an adjustable current threshold of 2-10 A per channel set by potentiometer. It isolates a faulted branch circuit without tripping the upstream 24 V supply.
Technical Specifications
| SKU | 6EP1961-2BA00 |
| Brand | Siemens |
| Series | SITOP select |
| Product designation | select, diagnosis module 4x10A |
| Input voltage (rated) | 24 V DC |
| Input voltage range | 22 ... 30 V DC |
| Input overvoltage capability | 35 V / 100 ms |
| Input current (rated, 24V) | 40 A |
| Number of outputs | 4 |
| Output current per channel, up to 60°C | 10 A |
| Adjustable overload threshold | 2 ... 10 A |
| Threshold setting | via potentiometer |
| Response delay, max. | 5 s |
| Efficiency | 97% |
| Power loss, typ. | 30 W |
| Overcurrent trip | Iout = 1.0-1.3x setpoint, trip after approx. 5 s |
| Current-limit trip | Iout = 1.3x setpoint, trip after approx. 50-100 ms |
| Immediate shutdown | Iout > setpoint and Vin < 20 V, trip after approx. 0.5 ms |
| Input fuse | Blade-type, 15 A per output (included) |
| Protection class IP | IP20 |
| MTBF at 40°C | 616,675 h |
| Enclosure (W x H x D) | 72 x 90 x 90 mm |
| Mounting | Snaps onto DIN rail EN 60715 35x7.5/15 |
| Net weight | 0.4 kg |
Certifications & Standards
- CE
- UKCA
- EAC
- CB
Selection Notes
The 2-10 A adjustable threshold and 4x10 A output split let this module protect four 24 V branch circuits from a single 40 A supply, tripping only the overloaded branch instead of the whole bus - the core selectivity function. Compare against lower-current selectivity module variants in the same family, sized for branch loads under 3 A per channel; pick this 6EP1961-2BA00 when individual loads run above 3 A per channel. The blade-type input fuse (15 A, user-replaceable) is the field-serviceable part after a sustained overcurrent event.
Applications
Used downstream of a central 24 V DC power supply to protect multiple independent control circuits - PLC I/O, sensor/actuator branches, valve manifolds - so a short on one branch does not shut down the whole cabinet.