- Description
The Siemens 6EP1931-2DC42 is a SITOP DC UPS module rated 24 V DC / 6 A output, drawing 22...29 V DC / 6 A at the input, that bridges mains power cuts with a connected battery module. It reaches 95% efficiency at rated output and adds a USB interface for status and configuration on top of floating relay contacts.
Technical Specifications
| SKU | 6EP1931-2DC42 |
| Brand | Siemens |
| Series | SITOP DC |
| Product Type Designation | DC UPS |
| Input Voltage | 22 ... 29 V DC (24 V DC rated) |
| Input Current at 24 V | 6 A (+ approx. 0.6 A with empty battery) |
| Output Voltage, Normal Operation | 24 V DC |
| Output Voltage, Buffering Mode | 19 ... 28.5 V DC |
| Output Current, Rated | 6 A |
| Peak Current | 6.3 A |
| Startup Delay Time | 1 s (typical) |
| Voltage Rise Time | 60 ms (typical) |
| Efficiency at Rated Output | 95% (typical) |
| Efficiency on Battery | 94.5% (typical) |
| Power Loss at Rated Output | 7 W (typical) |
| Supplied Active Power | 144 W (typical) |
| Interface | USB |
| Output Short-Circuit Proof | Yes |
| Reverse Polarity Protection | Input and battery |
| Protection Class IP | IP20 |
| Connection Method | Screw terminals |
| Ambient Temperature, Operation | -25 ... +60 degC (natural convection) |
| Enclosure Dimensions (W x H x D) | 50 x 125 x 125 mm |
| Fastening Method | DIN rail EN 60715 35x7.5/15 |
| Net Weight | 0.45 kg |
| MTBF at 40 degC | 904159 h |
Certifications & Standards
- CE
- cULus
- EAC
- ABS
- DNV
- EPD
Selection Notes
This is the 6 A member of the SITOP DC UPS family with a USB interface, which lets a PC log battery status and set the buffer response voltage instead of relying on the floating relay contacts alone. Pick the serial-interface variant if the downstream controller reads status over RS-232 rather than USB, or a higher-current variant in the same family when the load draws more than 6 A. The 1 s startup delay and 60 ms voltage rise time matter when sizing the module ahead of PLCs or drives that need a stable 24 V rail before they boot.
Applications
Bridges the 24 V DC control supply for PLCs, remote I/O, and HMI panels through short mains interruptions until standby generators start or the supply recovers, using a separately ordered battery module for energy storage.