- Home
- Power Quality, Metering & Power Supplies
- Siemens 6EP1434-2BA20 SITOP PSU300S 24V/10A 400-500V 3AC Power Supply Siemens 6EP1434-2BA20 SITOP PSU300S 24V/10A 400-500V 3AC Power Supply
Siemens 6EP1434-2BA20 SITOP PSU300S 24V/10A 400-500V 3AC Power Supply
Siemens 6EP1434-2BA20 SITOP PSU300S 24V/10A 400-500V 3AC Power Supply
Get Quote
- Description
The Siemens 6EP1434-2BA20 is a SITOP PSU300S stabilized power supply that converts 400-500 V 3 AC input into a regulated 24 V DC / 10 A output (240 W), with output voltage adjustable 24-28 V via potentiometer. It reaches 91% efficiency, tolerates input dips down to 340 V, and bridges a power failure for at least 7 ms at rated output current.
Technical Specifications
| SKU / Order No. | 6EP1434-2BA20 |
| Brand | Siemens |
| Series | SITOP PSU300S |
| Product Designation | Power supply SITOP smart, PSU300S |
| Input Type | 3-phase AC, wide range input |
| Input Voltage | 400-500 V (340-550 V operating range) |
| Line Frequency | 50/60 Hz (47-63 Hz) |
| Input Current | 0.7 A at 400 V / 0.6 A at 500 V |
| Output Voltage | 24 V DC, adjustable 24-28 V, isolated |
| Output Current | Rated 10 A, 0-10 A range (12 A up to +45 degC) |
| Output Power, typ. | 240 W |
| Efficiency | 91% |
| Power Loss, typ. | 23 W |
| Residual Ripple, max. | 200 mV |
| Buffering Time (rated output, min.) | 7 ms |
| Inrush Current Limit, max. | 20 A |
| Short-Circuit Protection | Yes, constant current characteristic |
| Overvoltage Protection | Vout < 35 V on internal fault |
| Protection Class | IP20, Class I |
| MTBF (40 degC) | 500,000 h |
| Ambient Temperature (Operation) | -25 to +70 degC, natural convection |
| Dimensions (W x H x D) | 70 x 125 x 120 mm |
| Net Weight | 0.7 kg |
Certifications & Standards
- CE
- UKCA
- EAC
- CB Certificate
- ABS
- DNV
- EPD
Selection Notes
The 10 A rated output (12 A up to 45 degC) and 240 W typical output power cover PLC racks, I/O, and 24 V field devices in one unit; step up to a higher-current SITOP model once the panel's continuous 24 V load exceeds this module's derated capacity. Two of these units can be run in parallel to raise available power or add redundancy, and Siemens redundancy, buffer, and selectivity modules from the same PSU300S family extend the base supply without replacing it.
Applications
Central 24 V DC supply for PLCs, remote I/O, sensors, and actuators fed from a 400-500 V 3 AC distribution board, including panels needing ABS/DNV marine classification for shipboard control systems.