- Home
- Power Quality, Metering & Power Supplies
- Schneider Electric METSEPM5570 PowerLogic PM5570 Class 0.2S 63rd Harmonic 2 Ethernet 2DI 2AI 2DO Power Meter Schneider Electric METSEPM5570 PowerLogic PM5570 Class 0.2S 63rd Harmonic 2 Ethernet 2DI 2AI 2DO Power Meter
Schneider Electric METSEPM5570 PowerLogic PM5570 Class 0.2S 63rd Harmonic 2 Ethernet 2DI 2AI 2DO Power Meter
Schneider Electric METSEPM5570 PowerLogic PM5570 Class 0.2S 63rd Harmonic 2 Ethernet 2DI 2AI 2DO Power Meter
Get Quote
- Description
The Schneider Electric METSEPM5570 is a PowerLogic PM5570 flush-mount power meter with Class 0.2S accuracy to IEC 62053-22 and 128 samples per cycle. It measures voltage, current, power, energy and harmonics to the 63rd order, monitors neutral current directly with calculated ground current, and adds two analog inputs alongside two digital inputs and two digital outputs for process integration.
Technical Specifications
| Reference | METSEPM5570 |
| Brand | Schneider Electric |
| Range | PowerLogic PM5000 |
| Device Short Name | PM5570 |
| Accuracy Class | Class 0.2S active energy (IEC 62053-22) |
| Power Quality Analysis | Up to the 63rd harmonic |
| Sampling Rate | 128 samples/cycle |
| Rated Supply Voltage (Us) | 90-528 V AC 45-65 Hz / 100-300 V DC |
| Rated Current Input (In) | 1 A or 5 A |
| Network Type | 1P+N, 3P, 3P+N |
| Measurement Voltage | 20-400 V AC phase-neutral / 20-828 V AC phase-phase |
| Metering Type | Measured neutral current, calculated ground current |
| Digital Inputs | 2 |
| Analog Inputs | 2 |
| Digital Outputs | 2 |
| Alarms | 52 configurable |
| Communication | RS485 Modbus RTU/ASCII; 2 x Ethernet RJ45, Modbus TCP/IP, BACnet/IP, DNP3 |
| Memory Capacity | 1.1 MB |
| Display | Monochrome graphic LCD, 128 x 128 px |
| Mounting | Flush-mounted, 96 x 96 mm |
| IP Rating | IP30 rear / IP54 display |
| Dimensions (W x D x H) | 96 x 72 x 96 mm |
| Weight | 0.45 kg |
Certifications & Standards
- CE
- cULus
- EN 50470-1
- EN 50470-3
- IEC 61557-12
- IEC 62053-22
- ANSI C12.20
Selection Notes
The PM5570 trades the PM5560's four digital inputs for a 2 DI / 2 AI mix, so it fits applications that need to bring in an analog transducer reading - a temperature or pressure sensor on a transformer, for example - alongside the standard WAGES pulse inputs on the same meter. Everything else in the PM5560/PM5570 base platform is identical, including Class 0.2S accuracy, 63rd-harmonic analysis and dual Ethernet, so the choice between the two comes down to whether the installation needs analog I/O or the full four digital-input count.