The Schneider Electric METSEPM5563 is a PowerLogic PM5563 DIN-rail power meter with Class 0.2S accuracy to IEC 62053-22 and no onboard display. It measures voltage, current, frequency, power factor and active/reactive power at 128 samples per cycle, resolves harmonics to the 63rd order, and monitors neutral current directly with calculated ground current. Dual Ethernet ports and an RS485 port carry Modbus, BACnet/IP and DNP3.
Technical Specifications
| Reference | METSEPM5563 |
| GTIN | 3606480614088 |
| Brand | Schneider Electric |
| Range | PowerLogic PM5000 |
| Device Short Name | PM5563 |
| Accuracy Class | Class 0.2S active energy (IEC 62053-22) |
| Power Quality Analysis | Up to the 63rd harmonic |
| Sampling Rate | 128 samples/cycle |
| Rated Supply Voltage (Us) | 90-528 V AC 45-65 Hz / 100-300 V DC |
| Rated Current Input (In) | 1 A or 5 A |
| Network Type | 1P+N, 3P, 3P+N |
| Measurement Voltage | 20-400 V AC phase-neutral / 20-828 V AC phase-phase |
| Metering Type | Measured neutral current, calculated ground current |
| Digital Inputs | 4, WAGES-capable |
| Digital Outputs | 2 |
| Alarms | 52 configurable |
| Display | None (DIN variant without display) |
| Communication | RS485 Modbus RTU/ASCII; 2 x Ethernet RJ45, Modbus TCP/IP, BACnet/IP, DNP3 |
| Memory Capacity | 1.1 MB |
| Mounting | Clip-on, DIN rail |
| IP Rating | IP30 rear |
| Dimensions (W x D x H) | 96 x 72 x 96 mm |
| Weight | 0.45 kg |
Certifications & Standards
- CE
- cULus
- BTL
- EN 50470-1
- IEC 61557-12
- IEC 62053-22
- ANSI C12.20
Selection Notes
The PM5563 is the DIN-rail, display-less counterpart to the flush-mount PM5560, so it fits auxiliary enclosures and metering cabinets where panel space for a 96 x 96 mm cutout is not available. Because it has no local LCD, readout depends entirely on the dual Ethernet ports and RS485 Modbus link, which is the right trade-off when the meter reports to a PME, BMS or SCADA system rather than being read on-site. Pick the METSEPM5563RD variant instead when a remote display is still needed at the panel face.