- Home
- Power Contactors (AC-3)
- Schneider Electric LC1E2501B5 Easy TeSys Contactor 3P 3NO AC-3 25 A 11 kW 24 V AC Coil Contactor Schneider Electric LC1E2501B5 Easy TeSys Contactor 3P 3NO AC-3 25 A 11 kW 24 V AC Coil Contactor
Schneider Electric LC1E2501B5 Easy TeSys Contactor 3P 3NO AC-3 25 A 11 kW 24 V AC Coil Contactor
Schneider Electric LC1E2501B5 Easy TeSys Contactor 3P 3NO AC-3 25 A 11 kW 24 V AC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1E2501B5 is a 3-pole Easy TeSys contactor rated 25 A AC-3 at up to 440 V, switching motors up to 11 kW at 415/440 V. It carries a 24 V AC 50 Hz coil and one built-in 1NC auxiliary contact, with power and control connections by screw clamp terminals in a 45.5 mm wide DIN-rail housing.
Technical Specifications
| SKU | LC1E2501B5 |
| Brand | Schneider Electric |
| Range | Easy TeSys |
| Poles | 3P, 3 NO |
| Utilisation Category | AC-3, AC-3e, AC-1 |
| [Ie] Rated Operational Current | 25 A at ≤440 V AC-3 |
| [Ue] Rated Operational Voltage | ≤690 V AC 50/60 Hz |
| Motor Power | 11 kW at 415/440 V AC |
| [Uc] Control Circuit Voltage | 24 V AC 50 Hz |
| [Ith] Conventional Free Air Thermal Current | 32 A at 55 °C |
| Rated Breaking Capacity | 212.5 A at 440 V (IEC 60947) |
| [Icw] Rated Short-Time Withstand Current | 240 A, 10 s at 40 °C |
| Associated Fuse Rating | 40 A gG at ≤690 V, coordination type 1 |
| Auxiliary Contact Composition | 1 NC |
| Maximum Operating Rate | 1800 cycles/hour |
| Mechanical/Electrical Durability | 10 Mcycles mechanical, 1.2 Mcycles AC-3 |
| Mounting Support | DIN rail or plate |
| IP Degree of Protection | IP2X (IEC 60529) |
| Permissible Ambient Operating Temperature | -5...55 °C |
| Height x Width x Depth | 74 x 45 x 85 mm |
| Net Weight | 0.36 kg |
Certifications & Standards
- CB Scheme
- CE
- CCC
- EAC
- EN/IEC 60947-1
- EN/IEC 60947-4-1
Selection Notes
The LC1E2501B5 covers 11 kW motors at 415/440 V with its 25 A AC-3 rating, needing only a 40 A gG fuse upstream for type-1 coordination. Its built-in 1NC contact wires directly into a stop or alarm circuit without an accessory block, and the 1.2 Mcycles AC-3 durability sits between the lower-current and higher-current steps of the same frame; for motors just below or above 11 kW, the adjacent current ratings of this contactor family are available.