- Home
- Power Contactors (AC-3)
- Schneider Electric LC1D95ED TeSys Deca Contactor 3P 3NO AC-3 95 A 48 V DC Coil Contactor Schneider Electric LC1D95ED TeSys Deca Contactor 3P 3NO AC-3 95 A 48 V DC Coil Contactor
Schneider Electric LC1D95ED TeSys Deca Contactor 3P 3NO AC-3 95 A 48 V DC Coil Contactor
Schneider Electric LC1D95ED TeSys Deca Contactor 3P 3NO AC-3 95 A 48 V DC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1D95ED is a TeSys Deca 3-pole (3NO) contactor rated 95 A AC-3 at up to 440 V, built for 45 kW motors at 400 V. It runs on a 48 V DC coil, with power connections on a 4-50 mm2 connector and control wiring on screw clamp terminals in the 85 mm frame.
Technical Specifications
| Reference | LC1D95ED |
| Brand | Schneider Electric |
| Range | TeSys Deca |
| Product Type | Contactor |
| Poles | 3P (3NO) |
| Utilisation Category | AC-1, AC-3, AC-3e, AC-4 |
| Rated Operational Voltage (Ue) | ≤ 690 V AC, 25-400 Hz |
| Rated Operational Current (Ie), AC-3, ≤440V | 95 A |
| Rated Operational Current (Ie), AC-1, ≤1000V | 125 A |
| Motor Power, AC-3 at 400 V | 45 kW |
| Control Circuit Voltage (Uc) | 48 V DC |
| Hold-In Power Consumption | 22 W |
| Rated Breaking Capacity at 440 V | 1100 A, IEC 60947 |
| Rated Short-Time Withstand Current (Icw), 1 s | 1100 A at 40 degrees C |
| Rated Insulation Voltage (Ui) | 1000 V, IEC 60947-4-1 |
| Auxiliary Contact Composition | 1 NO + 1 NC, mirror contact |
| Terminal Type | Connector 4-50 mm2 (power), screw clamp (control) |
| Maximum Operating Rate | 3600 cyc/h at 60 degrees C |
| Mounting | DIN rail or screw-fixing plate |
| IP Degree of Protection | IP20, front face |
| Dimensions (H x W x D) | 127 x 85 x 186 mm |
| Net Weight | 2610 g |
Certifications & Standards
- IEC 60947-4-1
- CCC
- EAC
- DNV-GL
- LROS
Selection Notes
At 95 A AC-3 and 45 kW at 400 V, the LC1D95ED runs a 48 V DC coil holding at 22 W, noticeably higher than the AC-coil D7/V7/Q7 siblings, and the extra coil hardware adds depth, extending the frame to 186 mm. It fits DC-control panels or battery-backed systems where the other 95 A LC1D variants with AC coils are not suitable. Breaking capacity and insulation rating match the rest of the 95 A LC1D family.