The Schneider Electric LC1D40ABNE is a TeSys Deca Advanced 3-pole (3NO) contactor rated 40 A AC-3 at up to 440 V, built for 18.5 kW motors at 400 V. A wide-range 24-60 V AC/DC electronic coil runs from either AC or DC control sources, while EverLink BTR screw connectors on the power circuit keep conductor terminations tight over time without retightening.
Technical Specifications
| Reference | LC1D40ABNE |
| Brand | Schneider Electric |
| Range | TeSys Deca Advanced |
| GTIN | 3606480988202 |
| Product Type | Contactor |
| Poles | 3P (3NO) |
| Utilisation Category | AC-1, AC-3, AC-3e, AC-4 |
| Rated Operational Voltage (Ue) | ≤ 690 V AC, 25-400 Hz |
| Rated Operational Current (Ie), AC-3, ≤440V | 40 A |
| Rated Operational Current (Ie), AC-1, ≤440V | 60 A |
| Motor Power, AC-3 at 400 V | 18.5 kW |
| Control Circuit Voltage (Uc) | 24-60 V AC/DC, electronic |
| Hold-In Power Consumption | 0.7 W |
| Rated Breaking Capacity at 440 V | 800 A, IEC 60947 |
| Rated Short-Time Withstand Current (Icw), 1 s | 720 A at 40 degrees C |
| Rated Insulation Voltage (Ui) | 690 V, IEC 60947-4-1 |
| Auxiliary Contact Composition | 1 NO + 1 NC, mirror contact |
| Terminal Type | EverLink BTR screw connectors (power), screw clamp (control) |
| Maximum Operating Rate | 3600 cyc/h at 60 degrees C |
| Mounting | DIN rail or screw-fixing plate |
| IP Degree of Protection | IP20, front face |
| Dimensions (H x W x D) | 122 x 55 x 120 mm |
| Net Weight | 992 g |
Certifications & Standards
- IEC 60947-4-1
- UL
- CSA
- CCC
- UKCA
Selection Notes
The LC1D40ABNE steps up to the 55 mm frame, where EverLink BTR power connectors accept conductors up to 35 mm² and maintain torque without the periodic retightening screw terminals need on vibration-prone machinery. Its 800 A breaking capacity at 440 V supports 110 A upstream circuit breaker coordination. Panels needing the same frame at higher current move to the 50 A or 65 A BNE variants without changing the mounting pattern.