- Home
- Power Contactors (AC-3)
- Schneider Electric LC1D38KUE TeSys Deca Advanced Contactor 3P 3NO AC-3 38 A 100-250 V AC/DC Coil Contactor Schneider Electric LC1D38KUE TeSys Deca Advanced Contactor 3P 3NO AC-3 38 A 100-250 V AC/DC Coil Contactor
Schneider Electric LC1D38KUE TeSys Deca Advanced Contactor 3P 3NO AC-3 38 A 100-250 V AC/DC Coil Contactor
Schneider Electric LC1D38KUE TeSys Deca Advanced Contactor 3P 3NO AC-3 38 A 100-250 V AC/DC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1D38KUE is a TeSys Deca Advanced 3-pole (3NO) contactor rated 38 A AC-3 at up to 440 V for 18.5 kW motors at 400 V. A sealed 100-250 V AC/DC electronic coil lets one part cover both AC and DC control rails, and 1NO+1NC mirror-certified auxiliary contacts are built in for status feedback. Screw clamp terminals serve both the power and control circuits.
Technical Specifications
| Reference | LC1D38KUE |
| Brand | Schneider Electric |
| Range | TeSys Deca Advanced |
| GTIN | 3606480987809 |
| Product Type | Contactor |
| Poles | 3P (3NO) |
| Utilisation Category | AC-1, AC-3, AC-3e |
| Rated Operational Voltage (Ue) | ≤ 690 V AC, 25-400 Hz |
| Rated Operational Current (Ie), AC-3, ≤440V | 38 A |
| Rated Operational Current (Ie), AC-1, ≤440V | 50 A |
| Motor Power, AC-3 at 400 V | 18.5 kW |
| Control Circuit Voltage (Uc) | 100-250 V AC/DC, electronic |
| Hold-In Power Consumption | 1.1 W |
| Rated Breaking Capacity at 440 V | 550 A, IEC 60947 |
| Rated Short-Time Withstand Current (Icw), 1 s | 430 A at 40 degrees C |
| Rated Insulation Voltage (Ui) | 690 V, IEC 60947-4-1 |
| Auxiliary Contact Composition | 1 NO + 1 NC, mirror contact |
| Terminal Type | Screw clamp (power and control) |
| Maximum Operating Rate | 3600 cyc/h at 60 degrees C |
| Mounting | DIN rail or screw-fixing plate |
| IP Degree of Protection | IP20, front face |
| Dimensions (H x W x D) | 85 x 45 x 101 mm |
| Net Weight | 442 g |
Certifications & Standards
- IEC 60947-4-1
- UL
- CSA
- CCC
- UKCA
Selection Notes
Specify the LC1D38KUE where the panel runs mixed control voltages: the 100-250 V AC/DC coil accepts 110 V, 230 V AC or common DC bus levels on one reference, which cuts spare-parts variety across a fleet of panels. It switches 18.5 kW at 400 V AC-3 with 550 A breaking capacity, and the depth grows slightly over the BNE wide-range version to house the sealed coil module. Lower-current needs point to the 18 A or 32 A KUE siblings on the same frame.