The Siemens 6ES7238-5XA32-0XB0 is a SIMATIC S7-1200 SM 1238 Energy Meter module that measures voltage, current, power, energy, and frequency in 1- and 3-phase TN/TT systems up to 480 V AC line-to-line. It accepts 1 A or 5 A current transformer inputs and reports voltage and current readings at 0.2 accuracy class per IEC 61557-12.
Technical Specifications
| SKU | 6ES7238-5XA32-0XB0 |
| Brand | Siemens |
| Series | SIMATIC S7-1200 |
| Product type designation | SM 1238, AI energy meter 480 V AC |
| Firmware version | V2.0.1 |
| Measurable line voltage, phase-neutral, max. | 293 V |
| Measurable line voltage, line-line, max. | 508 V |
| Current transformer range | 1 A / 5 A secondary |
| Continuous current, max. | 5 A |
| Frequency measurement range | 45-65 Hz |
| Accuracy class, voltage / current | 0.2 / 0.2 (IEC 61557-12) |
| Accuracy class, active power / active energy | 0.5 / 0.5 (IEC 61557-12) |
| Measurement category | CAT II (CAT III at 1.5 kV protection level) |
| Cycle time, all channels, typ. | 50 ms |
| Current consumption, max. | 180 mA |
| Power loss, typ. | 0.75 W |
| Address space per module, max. | 124 byte (112 input / 12 output) |
| Dimensions (W x H x D) | 45 x 100 x 75 mm |
| Weight, approx. | 165 g |
Certifications & Standards
- CE
- CSA
- UL
- cULus
- FM
- RCM
- KC
- Marine
Selection Notes
Match the connected current transformer's secondary rating to the module's 1 A or 5 A input range before wiring, since the 0.2 accuracy class for current is relative to that secondary rated current. The 0.5 accuracy class on active energy is adequate for sub-metering and load analysis inside TIA Portal but does not meet utility billing-grade requirements. CAT II input protection covers phase-to-neutral loads up to 293 V; select the CAT III-rated configuration (1.5 kV protection level) for line-to-line measurement points closer to the distribution feed.
Applications
Fits machine-level and panel-level energy sub-metering on 1- or 3-phase TN/TT systems up to 480 V AC, feeding voltage, current, power factor, and energy data directly into the S7-1200 program for local load monitoring, peak-demand logging, or forwarding to a plant energy management system over PROFINET.