- Home
- I/O Modules & Remote I/O
- Siemens 6ES7232-4HF50-0XB0 SIMATIC S7-1200 SM 1232 8AQ Analog Output PLC I/O Module Siemens 6ES7232-4HF50-0XB0 SIMATIC S7-1200 SM 1232 8AQ Analog Output PLC I/O Module
Siemens 6ES7232-4HF50-0XB0 SIMATIC S7-1200 SM 1232 8AQ Analog Output PLC I/O Module
Siemens 6ES7232-4HF50-0XB0 SIMATIC S7-1200 SM 1232 8AQ Analog Output PLC I/O Module
Get Quote
- Description
The Siemens 6ES7232-4HF50-0XB0 is a SIMATIC S7-1200 G2 SM 1232 analog output module with 8 channels, each delivering 14-bit voltage (±10V) or 13-bit current (0-20mA/4-20mA) output. It runs on 24V DC, dissipates 5.6W typical, and flags wire-break and short-circuit faults through onboard diagnostic LEDs, useful for catching an open output loop before it affects the process.
Technical Specifications
| SKU / Order Number | 6ES7232-4HF50-0XB0 |
| Brand | Siemens |
| Series | SIMATIC S7-1200 G2 |
| Product Type Designation | SM 1232, AQ 8x14 bit |
| Supply Voltage | 24 V DC (20.4 to 28.8 V) |
| Current Consumption | 45 mA (24V), 90 mA (5V backplane) |
| Power Loss | 5.6 W typ. |
| Number of Analog Outputs | 8, current or voltage |
| Output Range (Voltage) | -10V to +10V |
| Output Range (Current) | 0-20mA, 4-20mA |
| Resolution | 14 bit (voltage), 13 bit (current) |
| Load Impedance | ≥1000 Ω (voltage), ≤600 Ω (current) |
| Basic Error Limit | ±0.3% (voltage and current) |
| Diagnostics | Supply voltage, wire-break, short-circuit |
| Protection Rating | IP20 |
| Operating Temperature (Vertical) | -20 to 50°C |
| Dimensions (W x H x D) | 30 x 125 x 100 mm |
| Net Weight | 173 g |
Certifications & Standards
- CE
- UL
- cULus
- RCM
- KC
Selection Notes
Each of the 8 channels switches independently between ±10V voltage output and 0-20mA/4-20mA current output, so one module serves mixed proportional valve and analog display loads without matching modules to signal type in advance. The ≥1000 Ω minimum load on voltage outputs and ≤600 Ω maximum on current outputs set the actuator wiring limits — check cable run and actuator input impedance against these before sizing the loop. Short-circuit and wire-break diagnostics on every channel catch a disconnected actuator at the module rather than only downstream.
Applications
Analog setpoint outputs to proportional valves, VFD speed references, and analog process displays on SIMATIC S7-1200 G2 machine control panels.