- Home
- I/O Modules & Remote I/O
- Siemens 6ES7231-5PD50-0XB0 SIMATIC S7-1200 SM 1231 RTD AI 4x 16-Bit PLC I/O Module Siemens 6ES7231-5PD50-0XB0 SIMATIC S7-1200 SM 1231 RTD AI 4x 16-Bit PLC I/O Module
Siemens 6ES7231-5PD50-0XB0 SIMATIC S7-1200 SM 1231 RTD AI 4x 16-Bit PLC I/O Module
Siemens 6ES7231-5PD50-0XB0 SIMATIC S7-1200 SM 1231 RTD AI 4x 16-Bit PLC I/O Module
Get Quote
- Description
The Siemens 6ES7231-5PD50-0XB0 is a SIMATIC S7-1200 SM 1231 RTD signal module with 4 analog inputs for resistance thermometers, supporting Pt10 through Pt1000, Ni, Cu, and LG-Ni sensor types plus direct resistance measurement up to 600 ohms. Resolution is 15 bit plus sign, with 0.1 percent accuracy at 25 degrees C and a shielded cable length up to 100 m to the sensor.
Technical Specifications
| SKU | 6ES7231-5PD50-0XB0 |
| Brand | Siemens |
| Series | SIMATIC S7-1200 |
| Product Type Designation | SM 1231 RTD 4x 16 bit |
| Analog Inputs | 4, resistance thermometer |
| Supported Sensor Types | Pt10-Pt1000, Ni100-Ni1000, LG-Ni1000, Cu10-Cu100 |
| Resistance Ranges | 150, 300, 600 ohms |
| Resolution | 15 bit plus sign |
| Measurement Principle | Integrating, parameterizable integration time |
| Temperature Error (at 25 C) | plus/minus 0.1% of full-scale |
| Repeat Accuracy (at 25 C) | plus/minus 0.05% |
| Cable Length, shielded, max. | 100 m |
| Supply Voltage | 24 V DC, range 20.4-28.8 V |
| Current Consumption, typ. | 15 mA plus 65 mA from backplane bus |
| Power Loss, typ. | 0.6 W |
| Isolation, channels to power supply | Yes, tested at 707 V DC |
| Degree of Protection | IP20 |
| Dimensions (W x H x D) | 30 x 125 x 100 mm |
| Net Weight | 169 g |
Certifications & Standards
- CE
- UL
- cULus
- RCM
- KC
Selection Notes
The 4-channel RTD input and support for Pt10 through Pt1000, Ni, Cu, and LG-Ni sensor types let one module cover several probe standards without swapping hardware between projects using different temperature sensor brands. The 15-bit plus sign resolution with 0.1 percent accuracy at 25 degrees C suits closed-loop temperature control rather than simple threshold alarming. Because the integration time is parameterizable, a slower setting trades response speed for better noise rejection in electrically noisy cabinets, while a faster setting favors quick-changing process temperatures.
Applications
Temperature measurement in S7-1200-based machine and process control, including HVAC skids, extrusion and thermoforming lines, and any application using Pt100 or Pt1000 RTD probes for closed-loop temperature control.