- Home
- I/O Modules & Remote I/O
- Siemens 6ES7231-5PB50-0XB0 SIMATIC S7-1200 SB 1231 RTD AI 2x RTD Signal Board Siemens 6ES7231-5PB50-0XB0 SIMATIC S7-1200 SB 1231 RTD AI 2x RTD Signal Board
Siemens 6ES7231-5PB50-0XB0 SIMATIC S7-1200 SB 1231 RTD AI 2x RTD Signal Board
Siemens 6ES7231-5PB50-0XB0 SIMATIC S7-1200 SB 1231 RTD AI 2x RTD Signal Board
Get Quote
- Description
The Siemens 6ES7231-5PB50-0XB0 is a SIMATIC S7-1200 SB 1231 RTD signal board with 2 analog inputs for Pt100, Pt1000, Ni100, Ni1000, and other resistance-thermometer types, offering 15-bit plus sign resolution and +/-0.1% accuracy at 25 C. It supports cable runs up to 100 m shielded, provides 707 V DC isolation, carries an IP20 rating, and weighs only 29 g, mounting directly on the CPU's signal-board slot.
Technical Specifications
| SKU | 6ES7231-5PB50-0XB0 |
| Brand | Siemens |
| Series | SIMATIC S7-1200 |
| Analog Inputs | 2, resistance thermometer |
| Resolution | 15-bit + sign |
| Input Types | Pt10/50/100/200/500/1000, Ni100/120/200/500/1000, Cu10/50/100, LG-Ni1000, 150/300/600 ohm |
| Temperature Error (25 C) | +/-0.1% of full-scale |
| Temperature Error (-20 to 60 C) | +/-0.2% of full-scale |
| Repeat Accuracy (25 C) | +/-0.05% |
| Cable Length | 100 m shielded to sensor |
| Supply Current (backplane) | 20 mA typ. |
| Power Loss, typ. | 0.1 W |
| Isolation | 707 V DC, type test |
| IP Rating | IP20 |
| Dimensions (W x H x D) | 15 x 62 x 63 mm |
| Net Weight | 29 g |
Certifications & Standards
- CE mark
- UL approval
- cULus
- RCM
- KC approval
Selection Notes
The board reads 15 resistance-transmitter types (Pt, Ni, Cu, and raw resistance ranges) under a single ordering number, so the same board covers Pt100 and Pt1000 sensors without a separate SKU per sensor type - the type is selected in the hardware configuration, not at purchase. At 15 x 62 x 63 mm it mounts directly on the CPU's signal-board slot, adding RTD inputs without consuming a base-unit expansion slot or DIN-rail space. +/-0.1% accuracy at 25 C fits process-temperature monitoring rather than laboratory-grade calibration work.
Applications
Used for direct RTD temperature sensing - motor winding temperature, bearing temperature, process fluid temperature - on compact S7-1200 CPUs where a full I/O module isn't justified for two channels.