- Home
- I/O Modules & Remote I/O
- Siemens 6ES7222-5HH50-0XB0 SIMATIC S7-1200 SM 1222 16x Relay 2A PLC I/O Module Siemens 6ES7222-5HH50-0XB0 SIMATIC S7-1200 SM 1222 16x Relay 2A PLC I/O Module
Siemens 6ES7222-5HH50-0XB0 SIMATIC S7-1200 SM 1222 16x Relay 2A PLC I/O Module
Siemens 6ES7222-5HH50-0XB0 SIMATIC S7-1200 SM 1222 16x Relay 2A PLC I/O Module
Get Quote
- Description
The Siemens 6ES7222-5HH50-0XB0 SM 1222 is a SIMATIC S7-1200 digital output module with 16 relay outputs rated 2 A each, switched in two groups of 8. It runs from a 24 V DC backplane supply (20.4 to 28.8 V) and dissipates 4.2 W typical. IP20-rated, it mounts directly onto the S7-1200 backplane bus for machine control I/O expansion.
Technical Specifications
| Order No. (MLFB) | 6ES7222-5HH50-0XB0 |
| EAN | 4047623417361 |
| Brand | Siemens |
| Series | SIMATIC S7-1200 |
| Product Type Designation | SM 1222, DQ 16x relay/2 A |
| Supply Voltage (DC), rated | 24 V |
| Supply Voltage (DC), range | 20.4 V to 28.8 V |
| Input Current from Backplane Bus, max. | 115 mA |
| Number of Digital/Relay Outputs | 16, in groups of 8 |
| Switching Capacity, resistive load, max. | 2 A |
| Switching Capacity, lamp load, max. | 30 W DC / 200 W AC |
| Output Voltage (DC) | 5 V DC to 30 V DC |
| Output Voltage (AC) | 5 V AC to 250 V AC |
| Output Current for signal 1, rated | 2 A |
| Output Delay, resistive load, max. | 10 ms |
| Relay Operating Cycles, max. | 10 million mechanical; 100,000 at rated load voltage |
| Short-Circuit Protection | No; to be provided externally |
| Diagnostics Function | Yes; DIAG LED, output status LEDs |
| Degree of Protection | IP20 |
| Power Loss, typ. | 4.2 W |
| Ambient Temperature during Operation | -20C to 40C (vertical: to 50C, horizontal: to 60C) |
| Dimensions (W x H x D) | 30 mm x 125 mm x 100 mm |
| Weight, approx. | 217 g |
Certifications & Standards
- CE
- UL
- cULus
- RCM
- KC
Selection Notes
The 5HH50 variant uses electromechanical relay contacts, not transistor outputs, so it switches both AC loads (up to 200 W lamp load) and DC loads (up to 30 W) from the same module, which the transistor SM 1222 variants cannot do on the AC side. Short-circuit protection is not built in and must be added externally, since relay contacts cannot self-limit fault current the way a solid-state output can. The 16 outputs are grouped in two banks of 8 with channel isolation via the relays themselves, and mechanical life is rated for 10 million cycles unloaded versus 100,000 cycles at rated load, which sets the maintenance interval in high-cycle applications.
Applications
Relay-level digital output expansion on S7-1200 CPUs for switching contactors, solenoid valves, indicator lamps, and other AC or DC field loads within the 2 A / 250 V AC relay rating.