- Description
The Siemens SIMATIC S7-1200 SM 1222 (6ES7222-1BH32-1XB0) is a digital output module with 16 sinking (NPN transistor) outputs rated 24 V DC at 0.5 A each, drawing 140 mA from the backplane bus and dissipating 2.5 W. Short-circuit protection is not built in and must be provided externally on each output.
Technical Specifications
| SKU | 6ES7222-1BH32-1XB0 |
| Brand | Siemens |
| Series | SIMATIC S7-1200 |
| Product designation | SM 1222, DO 16x 24V DC/0.5A Sink |
| Supply voltage range | 20.4 ... 28.8 V DC |
| Backplane bus current draw, max. | 140 mA |
| Power loss, typ. | 2.5 W |
| Number of digital outputs | 16 |
| Output grouping | 1 per group |
| Output type | Current-sinking (NPN) |
| Short-circuit protection | No, external protection required |
| Output voltage (rated) | 24 V DC |
| Output current per channel (rated) | 0.5 A |
| Switching capacity, resistive load, max. | 0.5 A |
| Switching capacity, lamp load, max. | 5 W |
| Output delay, 0 to 1, max. | 20 µs |
| Output delay, 1 to 0, max. | 350 µs |
| Max. current per module, horizontal, up to 50°C | 8 A |
| Cable length, shielded, max. | 500 m |
| Cable length, unshielded, max. | 150 m |
| Diagnostic alarm | Yes |
| Degree of protection | IP20 |
| Operating temperature, horizontal | -20 ... 60 °C |
| Operating temperature, vertical | -20 ... 50 °C |
| Storage/transport temperature | -40 ... 70 °C |
| Dimensions (W x H x D) | 45 x 100 x 75 mm |
| Net weight | 220 g |
Certifications & Standards
- CE
- CSA
- UL
- cULus
- FM
- RCM
- KC
- Marine
Selection Notes
The current-sinking (NPN) output configuration pairs with sourcing-type field devices, which matters when matching this module to existing wiring - the sourcing-output SM 1222 variant in the same family is the counterpart for sinking-input field devices. Because short-circuit protection is not built in, each output needs external fusing or a protected load if there's a risk of a shorted field wire. The 8 A max. current per module at horizontal mounting, against the lower 50°C vertical-mount ambient limit, sets how many of the 16 outputs can run near full 0.5 A simultaneously.
Applications
Expands SIMATIC S7-1200 CPU digital output count for machines needing more than the CPU's onboard DO - solenoid valves, indicator lamps, small relays - wired to sinking-compatible loads.