- Home
- I/O Modules & Remote I/O
- Siemens 6ES7132-7HB00-0AB0 SIMATIC ET 200iSP 2DQ Relay 60V UC/2A Ex eb Remote I/O Module Siemens 6ES7132-7HB00-0AB0 SIMATIC ET 200iSP 2DQ Relay 60V UC/2A Ex eb Remote I/O Module
Siemens 6ES7132-7HB00-0AB0 SIMATIC ET 200iSP 2DQ Relay 60V UC/2A Ex eb Remote I/O Module
Siemens 6ES7132-7HB00-0AB0 SIMATIC ET 200iSP 2DQ Relay 60V UC/2A Ex eb Remote I/O Module
Get Quote
- Description
The Siemens 6ES7132-7HB00-0AB0 is a SIMATIC ET 200iSP electronic module with 2 relay digital outputs rated 60 V UC (AC/DC) at 2 A, approved Ex eb ib mb IIC T4 Gb for gas zones and Ex eb ib mb I Mb for mining. Reparameterization in RUN is supported, and it mounts on the ET200iSP rail with screw or spring terminals at IP30.
Technical Specifications
| Catalog No | 6ES7132-7HB00-0AB0 |
| SKU | 6ES7132-7HB00-0AB0 |
| Brand | Siemens |
| Series | SIMATIC ET 200iSP |
| Product type designation | 2DQ relay 60 V UC/2 A |
| HW functional status | 3 |
| Firmware version | V1.0.0 |
| Digital outputs | 2, relay |
| Output voltage type | AC/DC (UC) |
| Output current, signal 1, rated | 2 A |
| Switching capacity, resistive load, up to 60 degC, max. | 2 A |
| Thermal continuous current, max. | 2 A |
| Switching frequency, resistive load, max. | 100 Hz |
| Switching frequency, inductive load, max. | 2 Hz |
| Output delay 0 to 1 / 1 to 0, max. | 7 ms / 3 ms |
| Um, non-intrinsically safe terminals, max. | 250 V DC/AC |
| Reparameterization in RUN | Yes |
| ATEX marking | II 2 G and I M2 Ex eb ib mb IIC T4 Gb, Ex eb ib mb I Mb |
| Degree of protection | IP30 |
| Current consumption, typ. / max. | 100 mA / 120 mA |
| Power loss, typ. | 1.1 W |
| Cable length, shielded / unshielded, max. | 500 m / 500 m |
| Connection method | Screw/spring-type terminal |
| Dimensions (W x H x D) | 30 x 129 x 136.5 mm |
| Weight, approx. | 255 g |
Certifications & Standards
- GL
- ABS
- BV
- DNV
Selection Notes
This is the only relay-output module in the ET200iSP DQ lineup covered here, and its Ex eb ib mb protection combines increased safety (eb) with intrinsic safety (ib) and encapsulation (mb) rather than the ib-only rating on the transistor 4DQ modules - pick it when the field contact itself, not just the wiring, has to be Ex-rated. Because wire-break and short-circuit cannot be determined in the relay contact circuit, plan external monitoring if that diagnostic coverage is required. Reparameterization in RUN lets switching thresholds be adjusted without a CPU stop.