- Home
- PLC CPUs, Safety PLCs & Logic Modules
- Siemens 6ES7412-2EK07-0AB0 SIMATIC S7-400 CPU 412-2 PN 1MB MPI/DP PROFINET Programmable Logic Controller Siemens 6ES7412-2EK07-0AB0 SIMATIC S7-400 CPU 412-2 PN 1MB MPI/DP PROFINET Programmable Logic Controller
Siemens 6ES7412-2EK07-0AB0 SIMATIC S7-400 CPU 412-2 PN 1MB MPI/DP PROFINET Programmable Logic Controller
Siemens 6ES7412-2EK07-0AB0 SIMATIC S7-400 CPU 412-2 PN 1MB MPI/DP PROFINET Programmable Logic Controller
Get Quote
- Description
The Siemens 6ES7412-2EK07-0AB0 is a SIMATIC S7-400 CPU 412-2 PN central processing unit with 1 MB of work memory split 512 KB program / 512 KB data, and two interfaces: a 12 Mbit/s MPI/DP port and an Ethernet/PROFINET port. It supports up to 21 expansion units and multicomputing with up to 4 CPUs in one UR1 or UR2 rack.
Technical Specifications
| SKU | 6ES7412-2EK07-0AB0 |
| Brand | Siemens |
| Series | SIMATIC S7-400 |
| Product type designation | CPU 412-2 PN |
| Firmware version | V7.0 |
| Work memory, program | 512 KB |
| Work memory, data | 512 KB |
| Load memory, expandable FEPROM, max. | 64 MB (Memory Card) |
| Backup | Battery-backed, all data |
| CPU processing time, bit / word, typ. | 31.25 ns / 31.25 ns |
| DB / FB / FC, max. | 3000 / 1500 / 1500 |
| I/O address area, inputs / outputs | 4 KB / 4 KB |
| Digital channels, inputs / outputs | 32768 / 32768 |
| Analog channels, inputs / outputs | 2048 / 2048 |
| Number of expansion units, max. | 21 |
| Multicomputing | Yes, up to 4 CPUs (UR1/UR2) |
| Number of DP masters, integrated | 1 |
| Number of IO Controllers, integrated | 1 |
| Number of PROFIBUS/PROFINET CPs, recommended | 14 total |
| Power loss, typ. | 5.5 W |
| Net weight | 0.977 kg |
Certifications & Standards
- CE
- CSA
- UL
- cULus
- FM
- RCM
- KC
- EAC
Selection Notes
The -2 PN designation adds an integrated Ethernet/PROFINET port alongside the MPI/DP interface, so PROFINET IO devices connect directly to the CPU without a separate CP 443-1 module — choose this over a DP-only 412 CPU when the plant network is PROFINET-based. Multicomputing support for up to 4 CPUs in one UR1/UR2 rack lets a program split across CPUs when a single 1 MB work memory (512 KB program / 512 KB data) is not enough for the application; for programs that fit in one CPU, the simpler single-CPU rack layout is sufficient.
Applications
Suited to S7-400 rack-based process and machine control retrofits that need PROFINET IO connectivity without re-architecting an existing MPI/DP installation, and to multicomputing configurations that distribute a large control program across several CPUs sharing one backplane.