- Home
- New Arrivals
- Siemens 6BK1621-0AA00-0AA0 SIMATIC PN/BACnet LINK PROFINET to BACnet/IP Gateway IP20 Automation Component Siemens 6BK1621-0AA00-0AA0 SIMATIC PN/BACnet LINK PROFINET to BACnet/IP Gateway IP20 Automation Component
Siemens 6BK1621-0AA00-0AA0 SIMATIC PN/BACnet LINK PROFINET to BACnet/IP Gateway IP20 Automation Component
Get Quote
- Description
The Siemens 6BK1621-0AA00-0AA0 SIMATIC PN/BACnet LINK is a coupling module that bridges PROFINET to BACnet/IP fieldbus traffic, implementing the B-GW device profile at IP20. It runs PROFINET IO Device with an integrated 2-port switch on one side and a BACnet/IP interface supporting 1,000 objects and 1,000 subscription services on the other, powered from a 24 V DC supply.
Technical Specifications
| SKU | 6BK1621-0AA00-0AA0 |
| Brand | Siemens |
| Series | SIMATIC |
| EAN | 4025515739616 |
| Product type designation | PN/BACnet Link |
| Device profile | BACnet B-GW |
| Vendor ID | 7 |
| Engineering | STEP 7 TIA Portal from V14 SP1, GSDML V2.3.x |
| Mounting | DIN rail, wall mounting, portrait mounting |
| Supply voltage, rated | 24 V DC (20.4-28.8 V DC range) |
| Protection | Reverse polarity, overvoltage, short-circuit |
| Mains buffering time | 10 ms |
| Current consumption, rated / max. | 0.11 A / 0.13 A |
| Power loss, typ. | 2.7 W |
| PROFINET transmission rate, max. | 100 Mbit/s |
| PROFINET ports | 2x RJ45, integrated switch, 2x FastConnect |
| BACnet interface | BACnet/IP, isolated (1500 V AC / 2250 V DC) |
| BACnet objects / subscriptions | 1,000 / 1,000 |
| BACnet character set | ISO 10646 (UTF-8) |
| Diagnostics | RUN, ERROR, MAINT, LINK, RX/TX LEDs; status and alarm indication |
| Potential separation | Yes |
| IP degree of protection | IP20 |
| Ambient temperature, horizontal install | -25 to 60 °C |
| Ambient temperature, storage/transport | -40 to 85 °C |
| Relative humidity, max. | 95 % |
| Dimensions (W x H x D) | 70 x 112 x 75 mm |
| Weight, approx. | 210 g |
| Global warming potential, total | 50.8 kg CO2 eq |
| Country of origin | DE |
Certifications & Standards
- CE
- UL
- cULus
- RCM
- KC
- PNO
- BTL
- RoHS
Selection Notes
The B-GW device profile means this module acts as a routing gateway rather than a simple BACnet client: it exposes PROFINET IO process data as BACnet objects for a building management system while keeping the PROFINET side on its own integrated 2-port switch for line topology. The 10 ms mains-buffering time and reverse-polarity/overvoltage/short-circuit protection on the 24 V DC input let it sit on a shared control-cabinet supply without extra conditioning. Choose it specifically for PROFINET-to-BACnet/IP integration; it is not a general PROFINET switch or repeater.