- Home
- Motor Control & Protection
- Schneider Electric LUCL12ES TeSys U Standard Control Unit 3-12 A 48 V AC/48-72 V DC Motor Starter Module Schneider Electric LUCL12ES TeSys U Standard Control Unit 3-12 A 48 V AC/48-72 V DC Motor Starter Module
Schneider Electric LUCL12ES TeSys U Standard Control Unit 3-12 A 48 V AC/48-72 V DC Motor Starter Module
Schneider Electric LUCL12ES TeSys U Standard Control Unit 3-12 A 48 V AC/48-72 V DC Motor Starter Module
Get Quote
- Description
The Schneider Electric LUCL12ES is a TeSys U magnetic control unit that inserts into the LUB12, LUB32, and LUB38 power base to form a complete starter-controller for 3-phase motors up to 5.5 kW at 400-440 V AC. It gives adjustable short-circuit protection over a 3-12 A rated current range at an overcurrent threshold of 14.2 x Ir, and is powered from a 48 V AC / 48-72 V DC control circuit.
Technical Specifications
| Reference | LUCL12ES |
| Brand | Schneider Electric |
| Range | TeSys U |
| Device short name | LUCL |
| Product or component type | Magnetic control unit |
| Device application | Motor control, motor protection |
| Product compatibility | LUB12, LUB32, LUB38, LUB120, LUB320, LUB380 |
| Ue rated operational voltage | 690 V AC |
| Network frequency | 40...60 Hz |
| Utilisation category | AC-41, AC-43, AC-44 |
| Motor power | 5.5 kW at 400-440 V AC |
| Rated motor current adjustment range | 3-12 A |
| Tripping threshold | 14.2 x Ir +/- 20% |
| Uc control circuit voltage | 48 V AC / 48-72 V DC |
| Control circuit voltage limits | 0.8-1.1 Uc (AC), 0.8-1.1 Uc (DC) operational; 0.3-0.45 Uc drop-out |
| Ui rated insulation voltage | 690 V (IEC), 600 V (UL/CSA) |
| Uimp rated impulse withstand voltage | 6 kV |
| Fixing mode | Plug-in (front face) |
| Width x Height x Depth | 45 mm x 66 mm x 60 mm |
| Net weight | 0.135 kg |
| IP degree of protection | IP20 (front panel), IP40 (outside connection zone) |
| Ambient air temperature for operation | -25...70 C |
| Ambient air temperature for storage | -40...85 C |
| Operating altitude | 2000 m |
Certifications & Standards
- CE
- EAC
- ATEX
- EN 60947-6-2
- IEC 60947-6-2
- UL 60947-4-1
- CSA C22.2 No 60947-4-1
Selection Notes
Pick the LUCL12ES by matching its 3-12 A adjustment range to the full-load current of the motor, not the motor's nameplate power alone, since the dial sets the short-circuit trip point rather than an overload curve. The 48 V AC / 48-72 V DC control circuit voltage must match the coil supply available at the starter; overload protection itself is supplied separately by the drive or soft starter the unit is paired with, since this control module only provides short-circuit protection and manual reset.