- Home
- Motor Control & Protection
- Schneider Electric LC1E3210B5 Easy TeSys Contactor 3P 3NO AC-3 32 A 15 kW 24 V AC Coil Contactor Schneider Electric LC1E3210B5 Easy TeSys Contactor 3P 3NO AC-3 32 A 15 kW 24 V AC Coil Contactor
Schneider Electric LC1E3210B5 Easy TeSys Contactor 3P 3NO AC-3 32 A 15 kW 24 V AC Coil Contactor
Schneider Electric LC1E3210B5 Easy TeSys Contactor 3P 3NO AC-3 32 A 15 kW 24 V AC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1E3210B5 is a 3-pole Easy TeSys contactor rated 32 A AC-3 at up to 440 V, switching motors up to 15 kW at 415/440 V. It carries a 24 V AC 50 Hz coil and one built-in 1NO auxiliary contact, with power and control connections by screw clamp terminals in a 56 mm wide DIN-rail housing.
Technical Specifications
| SKU | LC1E3210B5 |
| Brand | Schneider Electric |
| Range | Easy TeSys |
| Poles | 3P, 3 NO |
| Utilisation Category | AC-3, AC-3e, AC-1 |
| [Ie] Rated Operational Current | 32 A at ≤440 V AC-3 |
| [Ue] Rated Operational Voltage | ≤690 V AC 50/60 Hz |
| Motor Power | 15 kW at 415/440 V AC |
| [Uc] Control Circuit Voltage | 24 V AC 50 Hz |
| [Ith] Conventional Free Air Thermal Current | 50 A at 55 °C |
| Rated Breaking Capacity | 272 A at 440 V (IEC 60947) |
| [Icw] Rated Short-Time Withstand Current | 260 A, 10 s at 40 °C |
| Associated Fuse Rating | 63 A gG at ≤690 V, coordination type 1 |
| Auxiliary Contact Composition | 1 NO |
| Maximum Operating Rate | 1800 cycles/hour |
| Mechanical/Electrical Durability | 8 Mcycles mechanical, 1 Mcycles AC-3 |
| Mounting Support | Plate or DIN rail |
| IP Degree of Protection | IP2X (IEC 60529) |
| Permissible Ambient Operating Temperature | -5...55 °C |
| Height x Width x Depth | 84 x 56 x 86 mm |
| Net Weight | 0.45 kg |
Certifications & Standards
- CB Scheme
- CE
- CCC
- EAC
- EN/IEC 60947-1
- EN/IEC 60947-4-1
Selection Notes
The LC1E3210B5 moves up to a 56 mm frame from the 45 mm bodies of the lower-current Easy TeSys contactors, sized for 15 kW motors at 415/440 V with a 63 A gG fuse for type-1 coordination. Its built-in 1NO contact suits run-indication wiring, and the 1 Mcycles AC-3 durability matches the heavier contact structure of this current step; for motors above 15 kW, the next current rating in this frame size is available.