- Home
- Motor Control & Protection
- Schneider Electric LC1D65AD7 TeSys Deca Contactor 3P 3NO AC-3 65 A 42 V AC Coil Contactor Schneider Electric LC1D65AD7 TeSys Deca Contactor 3P 3NO AC-3 65 A 42 V AC Coil Contactor
Schneider Electric LC1D65AD7 TeSys Deca Contactor 3P 3NO AC-3 65 A 42 V AC Coil Contactor
Schneider Electric LC1D65AD7 TeSys Deca Contactor 3P 3NO AC-3 65 A 42 V AC Coil Contactor
Get Quote
- Description
The Schneider Electric LC1D65AD7 is a TeSys Deca 3-pole (3NO) contactor rated 65 A AC-3 at up to 440 V, sized for 30 kW motors at 400 V. It uses a 42 V 50/60 Hz AC coil, a reduced control voltage common where panel design calls for a dedicated step-down transformer, and the power circuit lands on EverLink BTR screw connectors.
Technical Specifications
| Reference | LC1D65AD7 |
| Brand | Schneider Electric |
| Range | TeSys Deca |
| Product Type | Contactor |
| Poles | 3P (3NO) |
| Utilisation Category | AC-1, AC-3, AC-3e, AC-4 |
| Rated Operational Voltage (Ue) | ≤ 690 V AC, 25-400 Hz / ≤ 300 V DC |
| Rated Operational Current (Ie), AC-3, ≤440V | 65 A |
| Rated Operational Current (Ie), AC-1, ≤440V | 80 A |
| Motor Power, AC-3 at 400 V | 30 kW |
| Control Circuit Voltage (Uc) | 42 V AC, 50/60 Hz |
| Inrush Power | 160 VA |
| Rated Breaking Capacity at 440 V | 1000 A, IEC 60947 |
| Rated Short-Time Withstand Current (Icw), 1 s | 900 A at 40 degrees C |
| Rated Insulation Voltage (Ui) | 690 V, IEC 60947-4-1 |
| Auxiliary Contact Composition | 1 NO + 1 NC, mirror contact |
| Terminal Type | EverLink BTR screw connectors (power), screw clamp (control) |
| Maximum Operating Rate | 3600 cyc/h at 60 degrees C |
| Mounting | DIN rail or screw-fixing plate |
| IP Degree of Protection | IP20, front face |
| Dimensions (H x W x D) | 122 x 55 x 120 mm |
| Net Weight | 860 g |
Certifications & Standards
- IEC 60947-4-1
- UL
- CSA
- CCC
- Marine
Selection Notes
At the top of the 55 mm AC-coil frame, the LC1D65AD7 switches 30 kW motors at 400 V AC-3 with a 1000 A breaking capacity that coordinates with a 110 A upstream breaker. The 42 V coil keeps control-circuit voltage low for touch-safety requirements on exposed wiring runs. For the same current at 400 V or 48 V coil voltage, the AV7 and AE7 variants share the identical frame.