- Home
- Motor Control & Protection
- Schneider Electric GZ1LE07 Easy TeSys Power 3P 2.5 A ≥100 kA Magnetic Motor Protection Circuit Breaker (MPCB) Schneider Electric GZ1LE07 Easy TeSys Power 3P 2.5 A ≥100 kA Magnetic Motor Protection Circuit Breaker (MPCB)
Schneider Electric GZ1LE07 Easy TeSys Power 3P 2.5 A ≥100 kA Magnetic Motor Protection Circuit Breaker (MPCB)
Schneider Electric GZ1LE07 Easy TeSys Power 3P 2.5 A ≥100 kA Magnetic Motor Protection Circuit Breaker (MPCB)
Get Quote
- Description
The Schneider Electric GZ1LE07 is a 3-pole Easy TeSys Power motor circuit breaker with a fixed magnetic-only trip set at 2.5 A, giving a breaking capacity (Icu) of ≥100 kA at 400/415 V. It is DIN-rail mounted, operated by a push-button, and conforms to IEC 60947-2 and IEC 60947-4-1 for direct motor protection.
Technical Specifications
| Reference | GZ1LE07 |
| Brand | Schneider Electric |
| Range | Easy TeSys Power |
| Device short name | GZ1LE |
| Device application | Motor |
| Trip unit technology | Magnetic |
| Poles | 3P |
| Utilisation category | AC-3 (IEC 60947-2) |
| [In] rated current | 2.5 A |
| Magnetic tripping current | 33.5 A |
| Motor power at 400 V | 0.75 kW |
| Breaking capacity (Icu) at 400/415 V | ≥100 kA |
| Ics rated service breaking capacity (400/415 V) | 100% |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Power dissipation | 2.5 W per pole |
| Mounting | DIN rail, by clips or screws |
| Control type | Push-button |
| Connections - terminals | Screw clamp, 1-6 mm² solid / 1-4 mm² flexible with cable end |
| Dimensions (H x W x D) | 89 x 44.5 x 78 mm |
| Net weight | 0.25 kg |
| IP degree of protection | IP20 |
| Ambient air temperature (operation) | -20 to 60°C |
| Operating altitude | 2000 m |
Certifications & Standards
- CE
- CCC
- EAC
- EN/IEC 60947-2
Selection Notes
The GZ1LE07 has no thermal adjustment dial, so it only protects against short-circuit and severe overcurrent at the fixed 2.5 A magnetic threshold; it is specified where the motor already has separate thermal/overload protection (for example in a starter with a dedicated overload relay) and only short-circuit breaking is required from the breaker itself. For a lower rating, the GZ1LE06 is fixed at 1.6 A; for a higher one, the GZ1LE08 is fixed at 4 A. Where the motor needs its thermal protection built into the breaker, the equivalent GZ1E series in the same frame adds the adjustable thermal-magnetic trip.