- Schneider Electric GV2RT10 TeSys Deca 3P 4-6.3 A 100 kA Motor Protection Circuit Breaker (MPCB) Schneider Electric GV2RT10 TeSys Deca 3P 4-6.3 A 100 kA Motor Protection Circuit Breaker (MPCB)
Schneider Electric GV2RT10 TeSys Deca 3P 4-6.3 A 100 kA Motor Protection Circuit Breaker (MPCB)
Schneider Electric GV2RT10 TeSys Deca 3P 4-6.3 A 100 kA Motor Protection Circuit Breaker (MPCB)
Get Quote
- Description
The Schneider Electric GV2RT10 is a TeSys Deca (TeSys GV2) motor circuit breaker rated 4-6.3 A at 690 V AC, providing thermal-magnetic protection for 3-phase motors up to 2.2 kW at 400 V. It trips magnetically at 138 A, delivers a 100 kA breaking capacity at 400 V, and is operated by a toggle rated for 100,000 AC-3 cycles.
Technical Specifications
| SKU | GV2RT10 |
| Brand | Schneider Electric |
| Range | TeSys Deca (TeSys GV2) |
| Poles | 3P |
| Trip Unit Technology | Thermal-magnetic |
| Utilisation Category | Category A (IEC 60947-2), AC-3 (IEC 60947-4-1) |
| Thermal Protection Adjustment Range | 4-6.3 A |
| Line Rated Current (In) | 6.3 A |
| Magnetic Tripping Current | 138 A |
| Breaking Capacity (Icu) at 400/415 V | 100 kA |
| Motor Power at 400 V | 2.2 kW |
| Rated Operational Voltage (Ue) | 690 V AC, 50/60 Hz |
| Rated Insulation Voltage (Ui) | 690 V AC, 50/60 Hz |
| Rated Impulse Withstand Voltage (Uimp) | 6 kV |
| Control Type | Toggle |
| Connections | Screw clamp terminals, 1-6 mm² |
| Mounting | 35 mm DIN rail or panel with adaptor plate |
| Dimensions (W x H x D) | 45 x 89 x 78.5 mm |
| IP Degree | IP20 |
Certifications & Standards
- CE
- UKCA
- CCC
- cULus
- EAC
- EN/IEC 60947-2
- EN/IEC 60947-4-1
Selection Notes
The 4-6.3 A setting suits motors drawing up to 2.2 kW at 400 V; move to the adjacent setting in the GV2RT range as the full-load current falls outside this window, since the toggle, terminals and 690 V insulation are identical across the series. The full 100 kA breaking capacity at 400 V holds through this current band, so it can sit directly behind a high fault-current incomer without a separate current-limiter accessory.