- Description
The Schneider Electric LV481454 FuPacT GSD630 is a 4-pole switch disconnector fuse rated 630 A at up to 690 V AC, built for external front or right-side handle control. It takes DIN NH3 fuses and protects distribution circuits in buildings, infrastructure and industrial plants against short-circuits and overloads, with a 100 kA breaking capacity with fuses at 415 V and 690 V.
Technical Specifications
| SKU | LV481454 |
| Brand | Schneider Electric |
| Range | FuPacT |
| Product | FuPacT GS |
| Product type | Switch-disconnector-fuse |
| Poles | 4P |
| Number of fuse carriers | 4 |
| Fuse type / size | DIN NH3 |
| [Ue] Rated operational voltage | 690 V AC 50/60 Hz (1000 V AC AC-20) |
| [Ui] Rated insulation voltage | 1000 V AC |
| [Uimp] Rated impulse withstand voltage | 12 kV |
| [Ie] Rated operational current | 630 A at 220/240-660/690 V AC, AC-22A/AC-22B |
| [Iq] Breaking capacity with fuses | 100 kA at 415 V and 690 V AC |
| Rated operational power | 355 kW at 380/400 V; 295 kW at 660/690 V |
| Type of operating handle | External frontal, external right side |
| Mounting | Vertical, fixed, on backplate |
| Connections | Power circuit: bare cable connectors 63 mm²; lugs-ring terminals 2 cables 150 mm² or 2 cables 300 mm² |
| Tightening torque | 44 N.m |
| Dimensions (W x H x D) | 458 x 300 x 250 mm |
| Net weight | 20 kg |
| IP degree of protection | IP20 (with terminal cover) |
| Ambient temperature (operation) | -20...70 °C |
Certifications & Standards
- CE
- CCC
- EAC
- EN/IEC 60947-1
- EN/IEC 60947-3
Selection Notes
The GSD630 4P adds a fourth switched pole and internal neutral links to the 3-pole GSD630, for circuits needing a switched rather than solid neutral; it keeps the 3-pole version's 630 A rating, NH3 fuse size and 100 kA breaking capacity in a wider 458 mm housing. Choose the 3-pole variant where the neutral does not need to be switched. As with the 3-pole frame, only external frontal or right-side rotary handles are offered at this size, not a direct-mount handle.