- Home
- DIN Rail Power Supplies (24V DC)
- Schneider Electric ABLM1A24012 Modicon 24 V DC 1.25 A 1-Phase 100-240 V AC Regulated Power Supply Schneider Electric ABLM1A24012 Modicon 24 V DC 1.25 A 1-Phase 100-240 V AC Regulated Power Supply
Schneider Electric ABLM1A24012 Modicon 24 V DC 1.25 A 1-Phase 100-240 V AC Regulated Power Supply
Schneider Electric ABLM1A24012 Modicon 24 V DC 1.25 A 1-Phase 100-240 V AC Regulated Power Supply
Get Quote
- Description
The Schneider Electric ABLM1A24012 is a Modicon Power Supply range modular regulated switch-mode power supply delivering 24 V DC at 1.25 A from a 100-240 V AC single-phase input. Rated 30 W, it clips onto an omega DIN rail in a 36 mm wide housing and carries an internal 3.15 A fuse plus automatic-reset overload and short-circuit protection. A front LED confirms output voltage presence.
Technical Specifications
| Reference | ABLM1A24012 |
| GTIN | 3606481500151 |
| Brand | Schneider Electric |
| Range | Modicon Power Supply |
| Product Type | Power supply |
| Nominal Input Voltage | 100-240 V AC single phase |
| Rated Power | 30 W |
| Output Voltage | 24 V DC |
| Output Current | 1.25 A |
| Output Voltage Adjustment | 24-28 V |
| Efficiency | 87 % |
| Inrush Current | 25 A at 115 V / 50 A at 230 V |
| Power Dissipation | 5 W |
| Integrated Fuse | 3.15 A (not interchangeable) |
| Dimensions (W x H x D) | 36 x 91 x 55.6 mm |
| Mounting | Top hat TH35-15 / TH35-7.5 DIN rail (IEC 60715) |
| IP Degree of Protection | IP20 |
| Operating Temperature | -25 to 55 °C without derating (<2000 m) |
| MTBF | 2,500,000 h at 25 °C, full load |
| Net Weight | 0.170 kg |
Certifications & Standards
- CE
- CUL Listed
- CUL Recognized
- RCM
- CB Scheme
- EAC
- KC
- NEC class 2
- IEC 62368-1
- EN/IEC 61010-1
- EN 61010-2-201
- EN/IEC 61204-3
Selection Notes
The ABLM1A24012's 1.25 A / 30 W rating suits a mid-size group of 24 V DC devices, such as a PLC with several sensors and relays, in a 36 mm-wide DIN-rail slot. Drop to the 0.42 A or 0.625 A variants in the same Modicon Power Supply range for a lighter load, or step up to the 2.5 A unit for a larger one.