- Home
- DC UPS & Buffer Modules
- Siemens 6EP4137-3AB00-0AY0 SITOP UPS1600 24V/40A DC UPS Module Siemens 6EP4137-3AB00-0AY0 SITOP UPS1600 24V/40A DC UPS Module
Siemens 6EP4137-3AB00-0AY0 SITOP UPS1600 24V/40A DC UPS Module
Siemens 6EP4137-3AB00-0AY0 SITOP UPS1600 24V/40A DC UPS Module
Get Quote
- Description
The Siemens 6EP4137-3AB00-0AY0 is a SITOP UPS1600 DC uninterruptible power supply module rated for a 24 V DC / 40 A output (120 A peak), buffering the load from an external battery when the 24 V input drops below the adjustable cut-in threshold (21-25 V). Buffering time is set from 0.5 to 20 minutes via a rotary switch, at a typical 98.5% efficiency and 15 W power loss.
Technical Specifications
| SKU | 6EP4137-3AB00-0AY0 |
| Brand | Siemens |
| Series | SITOP UPS1600 |
| Type of current supply | DC UPS 24 V / 40 A |
| Input voltage (DC) | 21 ... 29 V, rated 24 V |
| Buffer connection cut-in threshold | Adjustable 21 ... 25 V (21, 21.5, 22, 22.5, 23, 24, 25 V) |
| Input current at rated 24 V | 46 A (incl. 5 A max. charging current) |
| Output voltage, normal/buffering | 24 V DC (18.5 ... 27 V in buffering mode) |
| Output current | 40 A rated, 0 ... 120 A operating range |
| Peak current | 120 A |
| Buffering time, adjustable | 0.5, 1, 2, 5, 10, 20 min (rotary switch) |
| Efficiency, typ. | 98.5% |
| Power loss, typ. | 15 W |
| Short-circuit protection | Yes, limited to 3x rated for 30 ms/min |
| Protection class / IP rating | Class III / IP20 |
| MTBF at 40 degrees C | 372,738 h |
| Ambient temperature, operation | -25 ... +70 degrees C, natural convection |
| Enclosure dimensions (W x H x D) | 70 x 139 x 150 mm |
| Net weight | 0.65 kg |
Certifications & Standards
- CE
- UL 508
- cULus
- UKCA
- EAC
- CB
- ABS Marine
- DNV Marine
Selection Notes
The 40 A rated / 120 A peak output sizes this UPS1600 for a 24 V DC bus feeding several PLCs, drives, or I/O racks through a mains dip, not just a single small controller - check total connected load against the 40 A continuous rating before specifying a smaller SITOP UPS in the same family. The rotary-switch buffering time (0.5-20 min) lets the same module cover both a short ride-through for controlled shutdown and a longer bridge while a generator starts, without reprogramming. Marine classification (ABS, DNV) makes it a fit for shipboard 24 V DC control panels where that approval is a spec requirement.
Applications
Bridges short mains interruptions on 24 V DC control and automation buses: PLC racks, drive control electronics, and instrumentation that must ride through brief supply dips or complete a controlled shutdown before battery reserve runs out.