- Description
The Siemens 6EP1933-2EC51 is a SITOP UPS500S basic unit, a maintenance-free capacitor-based DC UPS rated 24 V DC / 15 A output with a 5 kWs energy store, drawing 15.2 A at the 24 V DC input. It bridges 15 A for 9 s (or 5 A for 31 s) without a battery and adds a USB interface for status and configuration.
Technical Specifications
| SKU | 6EP1933-2EC51 |
| Brand | Siemens |
| Series | SITOP UPS500S |
| Product Type Designation | UPS500S |
| Energy Storage Type | Capacitors (5 kW.s) |
| Mains Buffering Time | 15 A for 9 s / 10 A for 15 s / 5 A for 31 s / 2 A for 76 s |
| Input Voltage | 22 ... 29 V DC (24 V DC rated) |
| Input Current at 24 V | 15.2 A (+ approx. 2.3 A with empty capacitor) |
| Output Voltage, Normal Operation | 24 V DC |
| Output Voltage, Buffering Mode | 24 ... 24.7 V DC |
| Output Current, Rated | 15 A |
| Peak Current | 25 A |
| Startup Delay Time | 0.6 s (typical) |
| Voltage Rise Time | 25 ms (typical) |
| Efficiency at Rated Output | 97.5% (typical) |
| Power Loss at Rated Output | 9 W (typical) |
| Supplied Active Power | 360 W (typical) |
| Interface | USB |
| Output Short-Circuit Proof | Yes |
| Reverse Polarity Protection | Input and energy storage |
| Protection Class IP | IP20 |
| Connection Method | Screw terminals |
| Ambient Temperature, Operation | 0 ... +60 degC (natural convection) |
| Enclosure Dimensions (W x H x D) | 120 x 125 x 125 mm |
| Fastening Method | DIN rail EN 60715 35x7.5/15 |
| Net Weight | 1 kg |
| MTBF at 40 degC | 459137 h |
Certifications & Standards
- CE
- cULus
- EAC
- ABS
- DNV
- EPD
Selection Notes
This is the basic UPS500S unit with a 5 kWs capacitor store, USB interface, and 15 A rated output, aimed at bridges measured in seconds rather than minutes: 15 A for 9 s or 5 A for 31 s. Because it uses capacitors, not a lead-acid battery module, there is no periodic battery replacement and the 97.5% efficiency exceeds the battery-based SITOP DC UPS modules. Add the SITOP UPS501S extension module when the application needs a longer buffering time than the basic unit alone provides.
Applications
Bridges brief 24 V DC dropouts for PLCs, drives, and remote I/O during supply switchover or short interruptions, where a maintenance-free capacitor store is preferred over a lead-acid battery.