- Home
- DC UPS & Buffer Modules
- Siemens 6EP1931-2EC21 SITOP DC UPS Module 24 V DC/15 A DC UPS Module Siemens 6EP1931-2EC21 SITOP DC UPS Module 24 V DC/15 A DC UPS Module
Siemens 6EP1931-2EC21 SITOP DC UPS Module 24 V DC/15 A DC UPS Module
Siemens 6EP1931-2EC21 SITOP DC UPS Module 24 V DC/15 A DC UPS Module
Get Quote
- Description
The Siemens SITOP 6EP1931-2EC21 is a 24 V DC uninterruptible power supply module rated for 15 A output current, drawing a 24 V/16 A DC input and bridging the connected load through an external battery module during a mains interruption. It reaches 96.2% efficiency at rated output and switches from mains to battery automatically once the input voltage falls below its adjustable 22-25.5 V threshold.
Technical Specifications
| SKU | 6EP1931-2EC21 |
| Brand | Siemens |
| Series | SITOP DC |
| Input Voltage | 24 V DC (22...29 V) |
| Input Current | 15 A rated (+approx. 1 A with empty battery) |
| Output Voltage | 24 V DC (normal and buffering mode) |
| Output Current | 15 A rated, 0...15 A range |
| Peak Current | 15.7 A |
| Buffer Connection Threshold | 22...25.5 V, adjustable in 0.5 V steps |
| Efficiency (rated output) | 96.2% typical |
| Efficiency (battery operation) | 96% typical |
| Power Loss | 14 W typical |
| Startup Delay | 1 s typical |
| Protection Class | IP20, Class III |
| Ambient Temperature (operation) | -25...+60 degrees C, natural convection |
| Mounting | DIN rail EN 60715 35x7.5/15 |
| Enclosure (W x H x D) | 50 x 125 x 125 mm |
| Net Weight | 0.4 kg |
| MTBF (40 degrees C) | 791,139 h |
Certifications & Standards
- CE
- EAC
- Shipbuilding
- ABS
- DNV
- EPD
Selection Notes
This is the 15 A-class module in the SITOP DC UPS line, sized for continuous loads up to 15 A, with the extra 1 A of input headroom reserved for battery charging rather than the load. It has no communication interface (design of interface: without), so status is read only through the floating relay contacts for OK, Alarm, and Bat>85% rather than over a network — choose the Ethernet/PROFINET SITOP UPS1600 instead when remote diagnostics are required. The 22-25.5 V adjustable buffer threshold, set in 0.5 V steps, lets the switch-to-battery point be tuned ahead of a downstream PLC's own undervoltage cutoff.
Applications
PLC and control-rack power backup for critical loops, short mains-dropout ride-through on production lines, and bridging power during automatic transfer switch operation.