- Home
- Contactor Relays & Auxiliary Contactors
- Schneider Electric CAE22B5 Easy TeSys Control Relay 2NO 2NC 24 V AC Coil Screw Clamp Auxiliary Contactor Schneider Electric CAE22B5 Easy TeSys Control Relay 2NO 2NC 24 V AC Coil Screw Clamp Auxiliary Contactor
Schneider Electric CAE22B5 Easy TeSys Control Relay 2NO 2NC 24 V AC Coil Screw Clamp Auxiliary Contactor
Schneider Electric CAE22B5 Easy TeSys Control Relay 2NO 2NC 24 V AC Coil Screw Clamp Auxiliary Contactor
Get Quote
- Description
The Schneider Electric CAE22B5 is an Easy TeSys control relay with 2NO+2NC contact composition and a 24 V AC coil, rated 10 A conventional thermal current (Ith) at up to 690 V. It switches AC-14/AC-15 electromagnetic loads for pilot-circuit control, rated for standard operating rates up to 180 cycles/min, with screw clamp terminals for DIN rail or panel mounting.
Technical Specifications
| Reference | CAE22B5 |
| Brand | Schneider Electric |
| Range | Easy TeSys |
| Product Type | Control Relay |
| Pole Contact Composition | 2NO+2NC |
| Utilisation Category | AC-14 / AC-15 |
| Rated Operational Voltage (Ue) | ≤690 V AC |
| Control Circuit Voltage (Uc) | 24 V AC |
| Conventional Thermal Current (Ith) | 10 A (at 40 °C) |
| Rated Making Capacity (Irms) | 140 A at 690 V AC (IEC 60947-5-1) |
| Rated Short-Time Withstand Current (Icw) | 120 A - 500 ms / 140 A - 100 ms |
| Rated Insulation Voltage (Ui) | 690 V (IEC 60947-5-1) |
| Control Circuit Voltage Limits | drop-out 0.3–0.6 Uc, operational 0.85–1.1 Uc @50 Hz |
| Maximum Operating Rate | 180 cyc/min |
| Inrush / Hold-in Power | 70 VA / 8 VA @50 Hz (20 °C) |
| Mounting | 35 mm DIN rail or screw-fixed mounting plate |
| Connections | Screw clamp terminals, 1–2.5 mm² |
| Dimensions (H × W × D) | 74 × 45 × 80 mm (H × W × D) |
| Net Weight | 0.28 kg |
| IP Degree of Protection | IP2X |
| Ambient Temperature | -20…+70 °C operation, -60…+80 °C storage |
Certifications & Standards
- CE
- CCC
- EAC
- BIS
- IEC 60947-5-1
Selection Notes
The 2NO+2NC contact set gives an equal number of make and break signals, useful for interlocking circuits that must mirror a command and its complement. This Easy TeSys range is certified CE, CCC, EAC and BIS but carries no UL or CSA listing, so it fits IEC-standard markets; panels that need UL 508 traceability for North America should use the TeSys K (CA2K) or TeSys Deca control relay instead. At 180 cycles/min maximum operating rate it suits standard-duty pilot switching rather than high-cycle automatic sequencing.