- Description
CAD50D7 is Schneider Electric's TeSys Deca control relay in a 5NO arrangement, built around a 42 V AC coil and a 140 A AC rated making capacity for up to 690 V circuits. Rated for AC-15/DC-13 duty between -40 and +60 °C, it duplicates and interlocks pilot signals in motor control circuits, terminating on screw clamp terminals on DIN rail or a mounting plate.
Technical Specifications
| Reference | CAD50D7 |
| Brand | Schneider Electric |
| Range | TeSys Deca |
| Product Type | Control Relay |
| Pole Contact Composition | 5NO |
| Utilisation Category | AC-14 / AC-15 / DC-13 |
| Rated Operational Voltage (Ue) | ≤690 V AC (25–400 Hz) |
| Control Circuit Voltage (Uc) | 42 V AC |
| Conventional Thermal Current (Ith) | 10 A (at 60 °C) |
| Rated Making Capacity (Irms) | 140 A AC / 250 A DC (IEC 60947-5-1) |
| Rated Short-Time Withstand Current (Icw) | 100 A - 1 s / 120 A - 500 ms / 140 A - 100 ms |
| Rated Insulation Voltage (Ui) | 690 V (IEC 60947-5-1) / 600 V (UL, CSA) |
| Control Circuit Voltage Limits | drop-out 0.3–0.6 Uc, operational 0.8–1.1 Uc @50 Hz / 0.85–1.1 Uc @60 Hz |
| Maximum Operating Rate | 180 cyc/min |
| Inrush / Hold-in Power | 70 VA / 8 VA @50 Hz (20 °C) |
| Mounting | 35 mm DIN rail or screw-fixed mounting plate |
| Connections | Screw clamp terminals, 1–4 mm² |
| Dimensions (H × W × D) | 77 × 45 × 84 mm (H × W × D) |
| Net Weight | 0.58 kg |
| IP Degree of Protection | IP2X (front face) |
| Ambient Temperature | -40…+60 °C operation (to 70 °C with derating), -60…+80 °C storage |
Certifications & Standards
- CE
- UKCA
- UL
- CSA
- CCC
- EAC
- IEC 60947-5-1
Selection Notes
Choose this 5NO variant for five make contacts, useful where one command must be duplicated to several downstream circuits without a break contact. The 42 V AC coil matches circuits already wired at that voltage, avoiding a separate step-down winding. The AC coil closes in 12–22 ms and draws 70 VA at inrush, dropping to 8 VA hold-in — the figure to size a shared control transformer against when several TeSys Deca relays operate together.