Schneider Electric's CA3KN22FD control relay carries 2NO+2NC contacts and a 110 V DC coil within the TeSys K range, rated 10 A conventional thermal current at up to 690 V. Rated for AC-15/DC-13 utilisation categories, it duplicates and interlocks pilot signals in control circuits, terminating on screw clamp terminals for DIN rail or screw-fixed mounting.
Technical Specifications
| Reference | CA3KN22FD |
| Brand | Schneider Electric |
| Range | TeSys K |
| Product Type | Control Relay |
| Pole Contact Composition | 2NO+2NC |
| Utilisation Category | AC-15 / DC-13 |
| Rated Operational Voltage (Ue) | ≤690 V (≤400 Hz) |
| Control Circuit Voltage (Uc) | 110 V DC |
| Conventional Thermal Current (Ith) | 10 A (at 50 °C) |
| Rated Making Capacity (Irms) | 110 A (IEC 60947) |
| Rated Insulation Voltage (Ui) | 690 V (IEC 60947) |
| Associated Fuse Rating | 10 A gG (IEC 60947 / VDE 0660) |
| Control Circuit Voltage Limits | drop-out 0.1–0.75 Uc, operational 0.8–1.15 Uc (≤50 °C) |
| Maximum Operating Rate | 10,000 cyc/h |
| Inrush / Hold-in Power | 3 W / 3 W (20 °C) |
| Mounting | 35 mm DIN rail or screw-fixed mounting plate |
| Connections | Screw clamp terminals, 1.5–4 mm² solid / 0.75–4 mm² flexible with cable end |
| Dimensions (H × W × D) | 58 × 45 × 57 mm (H × W × D) |
| Net Weight | 0.225 kg |
| IP Degree of Protection | IP2X |
| Ambient Temperature | -25…+50 °C operation, -50…+80 °C storage |
Certifications & Standards
- CE
- UKCA
- UL
- CSA
- CCC
- EAC
- IEC 60947-5-1
Selection Notes
With an equal number of make and break signals, useful for interlocking circuits that must mirror a command and its complement, the 2NO+2NC variant suits that specific wiring pattern. Specify the 110 V DC coil to match the plant's existing control voltage rather than adding a separate control transformer. The DC coil has no inrush surge and a longer 30–40 ms closing time than the AC-coil CA2Kseries, which electronic surge suppression trades for lower steady-state power draw — relevant when the relay is driven from a PLC transistor output or a current-limited 24 V DC rail.