- Home
- Contactor Relays & Auxiliary Contactors
- Schneider Electric CA2KN22F7 TeSys K Control Relay 2NO 2NC 110 V AC Coil Screw Clamp Auxiliary Contactor Schneider Electric CA2KN22F7 TeSys K Control Relay 2NO 2NC 110 V AC Coil Screw Clamp Auxiliary Contactor
Schneider Electric CA2KN22F7 TeSys K Control Relay 2NO 2NC 110 V AC Coil Screw Clamp Auxiliary Contactor
Schneider Electric CA2KN22F7 TeSys K Control Relay 2NO 2NC 110 V AC Coil Screw Clamp Auxiliary Contactor
Get Quote
- Description
Schneider Electric's CA2KN22F7 control relay carries 2NO+2NC contacts and a 110 V AC coil within the TeSys K range, rated 10 A conventional thermal current at up to 690 V. Rated for AC-15/DC-13 utilisation categories, it duplicates and interlocks pilot signals in control circuits, terminating on screw clamp terminals for DIN rail or screw-fixed mounting.
Technical Specifications
| Reference | CA2KN22F7 |
| Brand | Schneider Electric |
| Range | TeSys K |
| Product Type | Control Relay |
| Pole Contact Composition | 2NO+2NC |
| Utilisation Category | AC-15 / DC-13 |
| Rated Operational Voltage (Ue) | ≤690 V (≤400 Hz) |
| Control Circuit Voltage (Uc) | 110 V AC (AC 50/60 Hz) |
| Conventional Thermal Current (Ith) | 10 A (at 50 °C) |
| Rated Making Capacity (Irms) | 110 A (IEC 60947) |
| Rated Insulation Voltage (Ui) | 690 V (IEC 60947) |
| Associated Fuse Rating | 10 A gG (IEC 60947 / VDE 0660) |
| Control Circuit Voltage Limits | drop-out 0.2–0.75 Uc, operational 0.8–1.15 Uc (≤50 °C) |
| Maximum Operating Rate | 10,000 cyc/h |
| Inrush / Hold-in Power | 30 VA / 4.5 VA (20 °C) |
| Mounting | 35 mm DIN rail or screw-fixed mounting plate |
| Connections | Screw clamp terminals, 1.5–4 mm² solid / 0.75–4 mm² flexible with cable end |
| Dimensions (H × W × D) | 58 × 45 × 57 mm (H × W × D) |
| Net Weight | 0.18 kg |
| IP Degree of Protection | IP2X |
| Ambient Temperature | -25…+50 °C operation, -50…+80 °C storage |
Certifications & Standards
- CE
- UKCA
- UL
- CSA
- CCC
- EAC
- IEC 60947-5-1
Selection Notes
With an equal number of make and break signals, useful for interlocking circuits that must mirror a command and its complement, the 2NO+2NC variant suits that specific wiring pattern. Specify the 110 V AC coil to match the plant's existing control voltage rather than adding a separate control transformer. The AC coil pulls in within 10–20 ms and draws 30 VA at inrush, dropping to 4.5 VA hold-in, which is the standard figure to size a shared control transformer against when several of these relays switch together.