- Home
- Connectors, Plugs & Power Distribution
- Schneider Electric 81809 Mureva PK Panel-mounted Plug 16 A 3P+N+E 380-415 V IP44 Industrial Plug Schneider Electric 81809 Mureva PK Panel-mounted Plug 16 A 3P+N+E 380-415 V IP44 Industrial Plug
Schneider Electric 81809 Mureva PK Panel-mounted Plug 16 A 3P+N+E 380-415 V IP44 Industrial Plug
Schneider Electric 81809 Mureva PK Panel-mounted Plug 16 A 3P+N+E 380-415 V IP44 Industrial Plug
Get Quote
- Description
The Schneider Electric 81809 is a Mureva PK industrial plug rated 16 A at 380-415 V, configured three-phase with neutral, 3P+N+E. It is panel-mounted, uses 90-degree angled contacts set at the 6 h clock position, and carries an IP44 rating for use in washdown or outdoor industrial areas. The self-extinguishing polymer housing weighs 0.222 kg, in line with its current rating.
Technical Specifications
| Reference | 81809 |
| Brand | Schneider Electric |
| Range | Mureva PK |
| Device short name | Mureva plug |
| Product type | Plug |
| Poles | 3P+N+E |
| Network type | AC |
| Outlet standard | Industrial (IEC 60309) |
| Mounting mode | Panel-mounted |
| Shape | 90° angled |
| Rated current (In) | 16 A |
| Rated operational voltage (Ue) | 380-415 V |
| Network frequency | 50/60 Hz |
| Ground lug clock position | 6 h |
| Housing material | Self-extinguishing engineering polymer |
| Cable cross section | 1...4 mm2 |
| Colour | Red |
| Voltage colour code | Red |
| IP degree of protection | IP44 (IEC 60529) |
| IK degree of protection | IK08 (EN 62262) |
| Fire resistance | 850 degC (IEC 60695-2-11) |
| Mounting base dimensions | 90 x 100 mm |
| Dimensions (H x W x D) | 148 x 90 x 96 mm |
| Net weight | 0.222 kg |
Certifications & Standards
- EN 60309-1
- EN 60309-2
Selection Notes
This is the three-phase-with-neutral counterpart to the 16 A single-phase panel plug in the same IP44 range, for a control cabinet that needs both three-phase and single-phase circuits at light current. The IP44 rating fits an indoor panel rather than a washdown area, where the IP67 Mureva PK plugs in the range would be used instead.