Stoklink Technical Articles

MCB and Cable Coordination: the Ib Less Than In Less Than Iz Rule

What is the Ib ≤ In ≤ Iz rule for MCBs? It is the overload-coordination requirement in IEC 60364-4-43 that ties a breaker's rated current to both the load it feeds and the cable it protects, so the breaker trips before the cable insulation is damaged. Get the ordering wrong — set In above the cable's capacity Iz — and the MCB stops protecting the cable at all; it only protects the connected load. This article covers the rule's three terms, the second condition on conventional tripping current, why the cable and not the appliance is the thing actually at risk, a worked sizing example, and the fire-risk consequence of an oversized breaker on undersized cable.

The Coordination Rule in One Line

IEC 60364-4-43 Clause 433.1 sets the condition every final circuit must satisfy for overload protection: the design current must not exceed the rated current of the protective device, and the rated device current must not exceed the cable's current-carrying capacity.

Formula: Overload Coordination Rule — Source: IEC 60364-4-43, Clause 433.1

Ib ≤ In ≤ Iz

Symbol Description Unit
Ib Design current — the current the circuit is expected to carry in normal service A
In Rated current of the protective device (the MCB's nameplate rating) A
Iz Current-carrying capacity of the cable under actual installation conditions A

Three numbers, one inequality. Get any one of them out of order and the chain breaks — either the breaker trips on normal load (Ib > In), or it never trips before the cable overheats (In > Iz).

What Each Term Actually Means

Ib — Design Current

Ib is the current a circuit is expected to carry in normal service, calculated from the connected load, diversity factor, and duty cycle. For a socket-outlet ring it's an assumed diversified demand; for a fixed motor circuit it sits close to full-load current. Ib is a design number, not a measurement — pull it from the load schedule, not from a single clamp-meter reading.

Design current (Ib) is the current intended to be carried by a circuit in normal service, calculated from the connected load and any diversity factor applied (per IEC 60364-4-43).

In — Rated Current of the MCB

In is the nameplate rating stamped on the breaker — typically 6, 10, 16, 20, 25, 32, 40 or 63 A on standard MCB frames. It's fixed by the device, not adjustable on site, unlike an MCCB with an adjustable thermal-magnetic trip unit. Selecting In means picking the smallest catalog value at or above Ib, then checking that same value does not exceed Iz.

Iz — Cable Current-Carrying Capacity

Iz is not the cable's datasheet ampacity taken in isolation. It's that value after every installation correction factor has been applied: ambient temperature, grouping with other circuits, contact with thermal insulation, and installation method — clipped direct, in conduit, or buried. A 4 mm² cable rated 37 A in free air can drop to the mid-20s once grouped with several other circuits in a warm plant room.

Current-carrying capacity (Iz) is the maximum current a cable can carry continuously, under the actual installation conditions, without its steady-state temperature exceeding the rated limit for its insulation (per IEC 60364-5-52).
Key takeaway: Iz is a site-specific number, not a catalog value. Never size an MCB off the cable's free-air table rating — apply the grouping and temperature correction factors first, or the coordination check means nothing.

See our guide on MCB derating for temperature and grouping for the correction-factor tables used to get from tabulated rating to Iz.

The Second Condition: I2 ≤ 1.45 × Iz

Ib ≤ In ≤ Iz alone doesn't fully close the loop. IEC 60364-4-43 adds a second check: the current that guarantees the device actually operates within its conventional time — I2 — must not exceed 1.45 times Iz.

Formula: Conventional Tripping Current Condition — Source: IEC 60364-4-43, Clause 433.1 (I2 fixed per IEC 60898-1 for MCBs)

I2 ≤ 1.45 × Iz

Symbol Description Unit
I2 Conventional tripping current — the current that guarantees operation within the standard's conventional time; for MCBs, I2 = 1.45 × In, fixed by IEC 60898-1 A
Iz Current-carrying capacity of the cable under actual installation conditions A

For fuses, I2 varies by manufacturer and has to be read off a fusing curve. For MCBs to IEC 60898-1 it doesn't — the conventional tripping current is fixed by the product standard at 1.45 × In for every MCB, every curve, every manufacturer. That's what the conventional trip test in the standard verifies (1 hour up to 63 A, 2 hours above it).

Substitute that fixed relationship into the second condition: 1.45 × In ≤ 1.45 × Iz cancels down to In ≤ Iz — the first condition, already checked. What we see in the field: engineers trained on fuse boards sometimes go looking for I2 as a separate lookup on MCB circuits and get thrown when it always clears alongside the first condition. It isn't a coincidence. For MCBs the two conditions collapse into one because the standard fixes the 1.45 factor. The second condition earns its keep on fuse-protected circuits, where I2 is not a fixed multiple of In and has to be checked independently.

Key takeaway: For MCBs, satisfying In ≤ Iz automatically satisfies I2 ≤ 1.45 × Iz — the 1.45 × In conventional tripping current is fixed by IEC 60898-1, not something to look up per manufacturer.

Why the Rule Protects the Cable, Not the Load

An MCB downstream of a socket, motor starter, or distribution board doesn't know what's plugged in. It only sees the current flowing through its own poles. Set In too high relative to Iz and the breaker will hold a current the connected appliance would never draw — but that the cable feeding it cannot sustain.

Overcurrent protection does two distinct jobs, sized by two different numbers. The load-facing side lives in Ib: pick a device that won't nuisance-trip on start-up current or normal duty. The cable-facing side lives in Iz: pick a device that trips before the conductor's insulation ages past its rated life. In ≤ Iz is entirely about the second job. This depends on the load's inrush characteristic too — a C or D curve keeps the breaker from tripping during motor start, but the thermal element still has to respect Iz on sustained current, regardless of curve. Curve letter changes the instantaneous trip threshold, not the thermal one — see MCB tripping curves B, C, D, K and Z explained.

Worked Example

Circuit: a fixed load with a calculated design current Ib of 28 A. The feeder is 4 mm² PVC-insulated cable, clipped direct, grouped with three other circuits at 30°C ambient. Table-rated capacity for that cable size and method is 37 A; applying a grouping factor of 0.82 for four circuits gives Iz = 37 × 0.82 ≈ 30.3 A.

Candidate breaker ratings on the shelf: 25 A and 32 A. 25 A fails immediately — In (25) is less than Ib (28), so the breaker would trip under normal load. 32 A passes the first check — Ib (28) ≤ In (32) — but fails the second: In (32) exceeds Iz (30.3). The 32 A breaker fails coordination even though it comfortably clears Ib.

The fix is not a bigger breaker — it's a bigger cable, or fewer circuits in the group. Moving to 6 mm² cable at the same installation method and grouping raises Iz past 32 A, and the 32 A breaker now satisfies Ib (28) ≤ In (32) ≤ Iz. The conventional tripping check follows automatically: I2 = 1.45 × 32 = 46.4 A, and 1.45 × Iz now clears it too.

Key takeaway: When In ≤ Iz fails, don't jump to the next breaker size up — it makes the mismatch worse. Increase the cable size, reduce grouping, or improve the installation method until Iz clears the breaker rating needed for Ib.

What Happens When an MCB Is Oversized for the Cable

Skip the check and the failure mode is silent for years, then sudden. A cable rated Iz = 20 A protected by a 32 A MCB will carry a sustained 28-30 A overload — inside the load's normal draw, never touching the breaker's trip threshold — indefinitely. The bimetal thermal element only responds meaningfully once current climbs well past In; a cable running 40-50% over its rated capacity for months degrades its insulation through cumulative thermal aging, well before the breaker registers a fault condition.

PVC and XLPE insulation embrittle and crack under sustained overtemperature. Once cracked, insulation resistance drops, and the failure path is a slow-developing short or an arcing fault inside a wall cavity or cable tray — exactly the ignition source cable overload protection exists to prevent. An oversized MCB on an undersized cable does not fail safe. It removes the one safeguard meant to catch this condition.

Not always obvious at inspection, either. The breaker looks correctly rated against the panel schedule, the load looks normal, and nothing trips. The mismatch only shows up when someone checks Iz against In directly, or after the cable has already been damaged.

Selecting Iz-Compatible Ratings in Practice

Work the sizing in this order, not in reverse: calculate Ib from the load schedule, size the cable and apply every derating factor to get Iz, then pick the smallest standard In that is at or above Ib and at or below Iz. If no standard MCB rating fits between Ib and Iz, upsize the cable rather than the breaker — a breaker rated above Iz is not a valid substitute for a larger conductor.

For a full walk-through covering curve selection, breaking capacity, and pole configuration alongside this cable check, see our MCB selection checklist. Standards references for both the device and the installation rule are covered in IEC 60898-1 vs IEC 60947-2 standards compared. Browse rated devices across breaking capacities and curves in our miniature circuit breakers collection, and see the full sizing framework in the MCB engineering guide.

Frequently Asked Questions

What is Ib in MCB circuit design?

Ib is the design current — the current a circuit is expected to carry in normal service, calculated from the connected load and any diversity factor applied, per IEC 60364-4-43. It is a calculated value, not a field measurement.

How is Iz calculated for a cable?

Start with the cable's tabulated current rating for its size and installation method, then apply correction factors for ambient temperature, grouping with other circuits, and contact with thermal insulation, per IEC 60364-5-52. The result, not the tabulated value alone, is Iz.

Does the second condition, I2 ≤ 1.45 × Iz, ever matter separately for MCBs?

Rarely. Because IEC 60898-1 fixes the conventional tripping current at 1.45 × In for every MCB, satisfying In ≤ Iz automatically satisfies I2 ≤ 1.45 × Iz. The second condition is more relevant on fuse-protected circuits, where I2 varies by fuse type and has to be checked independently.

What if no standard MCB rating fits between Ib and Iz?

Increase the cable size or reduce the derating factors — less grouping, better ventilation, shorter run through insulation — until Iz rises above a standard In that also clears Ib. Do not select a breaker above Iz to fill the gap.

Why is an oversized MCB dangerous even if it never trips?

Because never tripping is the problem, not the reassurance. A breaker rated above the cable's Iz lets the cable run in sustained overload without ever reaching the breaker's thermal trip threshold, aging the insulation until it cracks or arcs — a fire-risk condition the breaker was supposed to prevent.

Conclusion

Ib ≤ In ≤ Iz is not a formality for the panel schedule — it decides whether the MCB protects the cable or just rides along with it. For MCBs, the second condition on conventional tripping current collapses into the first because IEC 60898-1 fixes I2 at 1.45 × In. That leaves one number to get right on every circuit: In has to sit between the load's design current and the cable's derated capacity, not above it. Skip that check and the breaker becomes decorative — the cable carries the risk instead.

Comments (0)

    Leave a comment