VFD for Compressors: Selection Guide
How to select and size a VFD for screw, reciprocating and centrifugal compressors, covering overload rating, turndown limits and energy savings.
SINAMICS G120C variable frequency drive, 4.00 kW, 380-480 V 3AC, IP20 / UL open type.
The Siemens 6SL3210-1KE18-8UF1 is a SINAMICS G120C variable frequency drive (VFD) rated 4 kW for 380-480 V 3 AC supply. It delivers 11.4 A rated output current with V/f and sensorless vector control, integrated PROFINET, EtherNet/IP communication, Safe Torque Off (STO), and IP20 / UL open type protection for control-cabinet mounting.
The 6SL3210-1KE18-8UF1 is designed for general machine building — pumps, fans, compressors, conveyors, mixers and extruders — combining a compact footprint with integrated PROFINET connectivity and Safe Torque Off for safety-rated machinery.
Genuine Siemens product supplied by Stoklink with fast dispatch from Türkiye.
| Input: Number of phases | 3 AC |
|---|---|
| Input: Line voltage | 380 ... 480 V +10 % -20 % |
| Input: Line frequency | 47 ... 63 Hz |
| Input: Rated current (LO) | 11.40 A |
| Input: Rated current (HO) | 10.60 A |
| Output: Number of phases | 3 AC |
| Output: Rated voltage | 400V IEC / 480V NEC 1) |
| Output: Rated power (LO) | 4.00 kW / 5.00 hp |
| Output: Rated power (HO) | 3.00 kW / 4.00 hp |
| Output: Rated current (LO) | 8.80 A |
| Output: Rated current (HO) | 7.30 A |
| Output: Rated current (IN) | 9.00 A |
| Output: Max. output current | 14.60 A |
| Output: Pulse frequency | 4 kHz |
| Output: Output frequency for vector control | 0 ... 240 Hz |
| Output: Output frequency for V/f control | 0 ... 550 Hz |
| Low Overload (LO) | 150 % base load current IL for 3 s, followed by 110 % base load current IL for 57 s |
| High Overload (HO) | 200% base load current IH for 3 s, followed by 150% base load current IH for 57 s |
| Power factor λ | 0.70 ... 0.85 |
|---|---|
| Offset factor cos φ | 0.95 |
| Efficiency η | 0.97 |
| Sound pressure level (1m) | 52 dB |
| Filter class (integrated) | Unfiltered |
| Communication | PROFINET, EtherNet/IP |
|---|
| Part number | 6SL3210-1KE18-8UF1 |
|---|---|
| Brand | Siemens |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| EAN | 4042948663950 |
| Standard digital inputs: Number | 6 |
|---|---|
| Standard digital inputs: Switching level: 0→1 | 11 V |
| Standard digital inputs: Switching level: 1→0 | 5V |
| Standard digital inputs: Max. inrush current | 15 mA |
| Fail-safe digital inputs: Number | 1 |
| Digital outputs: Number as relay changeover contact | 1 |
| Digital outputs: Output (resistive load) | DC 30 V, 0.5 A |
| Digital outputs: Number as transistor | 1 |
| Analog / digital inputs: Number | 1 (Differential input) |
| Analog / digital inputs: Resolution | 10 bit |
| Switching threshold as digital input: 0→1 | 4V |
| Switching threshold as digital input: 1→0 | 1.6 V |
| Analog outputs: Number | 1 (Non-isolated output) |
| PTC/ KTY interface | 1 motor temperature sensor input, sensors that can be connected PTC, KTY and |
| V/f linear / square-law / parameterizable | 1 |
|---|---|
| V/f with flux current control (FCC) | 1 |
| V/f ECO linear / square-law | 1 |
| Sensorless vector control | 1 |
| Vector control, with sensor | 0 |
| Encoderless torque control | 0 |
| Torque control, with encoder | 0 |
| Page 1 of 2 | Generated Sun Nov 1 00:43:16 CET 2026 |
| Cooling | Air cooling using an integrated fan |
|---|---|
| Cooling air requirement | 0.005 m³/s (0.177 ft³/s) |
| Installation altitude | 1,000 m (3,280.84 ft) |
| Ambient temperature: Operation | -10 ... 40 °C (14 ... 104 °F) |
| Ambient temperature: Transport | -40 ... 70 °C (-40 ... 158 °F) |
| Ambient temperature: Storage | -25 ... 55 °C (-13 ... 131 °F) 95 % At 40 °C (104 °F), condensation 0.15 ... 1.50 mm² (AWG 24 ... AWG 16) |
| Line side: Version | Plug-in screw terminals 1.00 ... 2.50 mm² (AWG 18 ... AWG 14) |
|---|---|
| Motor end: Version | Plug-in screw terminals 1.00 ... 2.50 mm² (AWG 18 ... AWG 14) |
| DC link (for braking resistor): Version | Plug-in screw terminals 1.00 ... 2.50 mm² |
| Line length, max. | (AWG 18 ... AWG 14) 15 m (49.21 ft) |
| PE connection | On housing with M4 screw |
| Max. motor cable length: Shielded | 150 m (492.13 ft) |
| Max. motor cable length: Unshielded | 150 m (492.13 ft) |
| Degree of protection | IP20 / UL open type |
|---|---|
| Frame size | FSA |
| Dimensions: Width | 73 mm (2.87 in) |
| Dimensions: Height | 196 mm (7.72 in) |
| Dimensions: Depth | 200 mm (8.19 in) |
| Compliance with standards | CE, cUL, UL, KC, EAC, C-Tick (RCM) EMC Directive 2004/108/EC, Low- Voltage Directive 2006/95/EC |
|---|
| Net weight | 1.7 kg |
|---|---|
| Shipping weight | 2.6 kg |
| Ships from | Türkiye |
| Dispatch | 18 Nov |
| Stock | In stock |
Source: manufacturer data · Last verified: 31 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of 6SL3210-1KE18-8UF1 is 11.40 A.
The rated operational voltage of 6SL3210-1KE18-8UF1 is 380–480 V AC.
The rated motor power of 6SL3210-1KE18-8UF1 is 4.00 kW.
The EAN (GTIN) of 6SL3210-1KE18-8UF1 is 4042948663950.
6SL3210-1KE18-8UF1 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1–2 business days.
How to select and size a VFD for screw, reciprocating and centrifugal compressors, covering overload rating, turndown limits and energy savings.
Size your VFD correctly with our complete guide covering FLA calculation, duty cycle, derating, harmonics, and brand-specific sizing tables. Shop at Stoklink.
Compare VFD types including VSI, CSI, PWM, and matrix converters with selection criteria, harmonic data, and real installation examples. Shop at Stoklink.