Contactors for Data Center PDU and UPS Systems: Selection Guide
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
The Siemens 3RT1065-6AP36 is a 3-pole SIRIUS 3RT1 contactor rated 265 A (AC-3) / 132 kW at 400 V, 200 hp at 480 V, with a 220–240 V AC/DC coil and 2 NO + 2 NC auxiliary contacts.
The Siemens 3RT1065-6AP36 is a contactor from the SENTRON/SIRIUS 3RT1 series. Power contactor, AC-3e/AC-3 265 A, 132 kW / 400 V AC (50-60 Hz) / DC Uc: 220-240 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: screw terminal. Supplied by Stoklink for industrial and commercial low-voltage applications.
The Siemens 3RT1065-6AP36 is used in industrial control panels, distribution boards and automation systems. As part of the Siemens 3RT1 range it integrates with compatible SENTRON/SIRIUS components for a coordinated low-voltage installation. Genuine Siemens product supplied by Stoklink with fast dispatch from Türkiye.
| Series | SIRIUS 3RT1 |
|---|---|
| Contactor size / frame | S10 |
| Number of poles | 3 |
| Main contact configuration | 3 NO |
| Rated operational current Ie, AC-3, 400 V | 265 A |
|---|---|
| Rated motor power, AC-3, 400 V | 132 kW |
| Rated operational current, AC-1 (60 °C) | 300 A |
| Rated operational current, AC-1 (40 °C) | 330 A |
| Rated operational current, AC-4, 400 V | 230 A |
| Max. rated operational voltage Ue | 1000 V |
| Rated insulation voltage Ui | 1000 V |
| Rated impulse withstand voltage Uimp | 8 kV |
| Rated control supply voltage Uc | 220–240 V |
|---|---|
| Coil type | AC-DC |
| Coil frequency | 50/60 Hz |
| Coil technology | Conventional, surge suppressor with varistor |
| Coil holding power | 7.4 W | VA |
| Part number | 3RT1065-6AP36 |
|---|---|
| Model code | S10 |
| Brand | Siemens |
| Series | SIRIUS 3RT1 |
| Family | Contactors |
| Condition | New, factory sealed |
| Source | Siemens and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 4011209507937 |
| ETIM class | EC000066 |
| eCl@ss | 27371003 |
| UPC | 754554772493 |
| UNSPSC | 39121529 |
| Built-in auxiliary contacts, NO | 2 |
|---|---|
| Built-in auxiliary contacts, NC | 2 |
| Auxiliary contacts | 2 NO + 2 NC |
| Mirror contact (IEC 60947-4-1 Annex F) | Yes |
| Main circuit connection | Busbar |
|---|---|
| Mounting | Panel (screw) mounting |
| Width | 145 mm |
|---|---|
| Height | 210 mm |
| Depth | 202 mm |
| Net weight | 6.162 kg |
| Ambient operating temperature | -25 … 60 °C |
|---|---|
| Degree of protection | IP00; IP20 with box terminal/cover |
| Mechanical durability | 10000000 cycles |
| Max. operating frequency, AC-3 | 500 cycles/h |
| Motor rating (UL/CSA) | 75 hp @ 200/208 V · 100 hp @ 220/230 V · 200 hp @ 460/480 V · 250 hp @ 575/600 V |
|---|---|
| Full-load amps @ 480 V | 240 A |
| Certifications | UL, Marine |
|---|
| Package dimensions (L × W × H) | 281 × 201 × 235 mm |
|---|---|
| Shipping weight | 7.162 kg |
| Ships from | Türkiye |
| Dispatch | 16 Nov |
| Stock | In stock |
| product brand name | SIRIUS |
|---|---|
| product designation | Power contactor |
| product extension · function module for communication | No |
| product extension · auxiliary switch | Yes |
| power loss [W] for rated value of the current · at AC in hot operating state | 54 W |
| power loss [W] for rated value of the current · without load current share typical | 7.4 W |
| type of calculation of power loss current-dependent | quadratic |
| insulation voltage · of auxiliary circuit with degree of pollution 3 rated value | 500 V |
| surge voltage resistance · of auxiliary circuit rated value | 6 kV |
| maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1 | 690 V |
| shock resistance at rectangular impulse · at AC | 8,5 g / 5 ms, 4,2 g / 10 ms |
| shock resistance at rectangular impulse · at DC | 8,5 g / 5 ms, 4,2 g / 10 ms |
| shock resistance with sine pulse · at AC | 13,4 g / 5 ms, 6,5 g / 10 ms |
| shock resistance with sine pulse · at DC | 13,4 g / 5 ms, 6,5 g / 10 ms |
| mechanical service life (operating cycles) · of the contactor with added electronically optimized auxiliary switch block typical | 5 000 000 |
| reference code according to IEC 81346-2 | Q |
| Substance Prohibitance (day/month/year) | 05/01/2012 |
| SVHC substance name | Lead CAS-No. 7439-92-1 |
| installation altitude at height above sea level maximum | 2 000 m |
| ambient temperature · during storage | -55 ... +80 °C |
| relative humidity minimum | 10 % |
| relative humidity at 55 °C according to IEC 60068-2-30 maximum | 95 % |
| number of NC contacts for main contacts | 0 |
| operating voltage · at AC-3e rated value maximum | 1 000 V |
| operational current · at AC-1 · up to 690 V at ambient temperature 40 °C rated value | 330 A |
| operational current · at AC-1 · up to 1000 V at ambient temperature 40 °C rated value | 150 A |
| operational current · at AC-3 · at 500 V rated value | 265 A |
| operational current · at AC-3 · at 690 V rated value | 265 A |
| operational current · at AC-3 · at 1000 V rated value | 95 A |
| operational current · at AC-3e · at 400 V rated value | 265 A |
| operational current · at AC-3e · at 500 V rated value | 265 A |
| operational current · at AC-3e · at 690 V rated value | 265 A |
| operational current · at AC-3e · at 1000 V rated value | 95 A |
| operational current · at AC-5a up to 690 V rated value | 290 A |
| operational current · at AC-5b up to 400 V rated value | 219 A |
| operational current · at AC-6a · up to 230 V for current peak value n=20 rated value | 265 A |
| operational current · at AC-6a · up to 400 V for current peak value n=20 rated value | 265 A |
| operational current · at AC-6a · up to 500 V for current peak value n=20 rated value | 265 A |
| operational current · at AC-6a · up to 690 V for current peak value n=20 rated value | 265 A |
| operational current · at AC-6a · up to 1000 V for current peak value n=20 rated value | 95 A |
| minimum cross-section in main circuit at maximum AC-1 rated value | 185 mm2 |
| operational current for approx. 200000 operating cycles at AC-4 · at 400 V rated value | 117 A |
| operational current · at 1 current path at DC-1 · at 24 V rated value | 300 A |
| operational current · at 1 current path at DC-1 · at 60 V rated value | 300 A |
| operational current · at 1 current path at DC-1 · at 110 V rated value | 33 A |
| operational current · at 1 current path at DC-1 · at 220 V rated value | 3.8 A |
| operational current · at 1 current path at DC-1 · at 440 V rated value | 0.9 A |
| operational current · at 1 current path at DC-1 · at 600 V rated value | 0.6 A |
| operational current · with 2 current paths in series at DC-1 · at 24 V rated value | 300 A |
| operational current · with 3 current paths in series at DC-1 · at 24 V rated value | 300 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 24 V rated value | 300 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 60 V rated value | 11 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 110 V rated value | 3 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 220 V rated value | 0.6 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 440 V rated value | 0.18 A |
| operational current · at 1 current path at DC-3 at DC-5 · at 600 V rated value | 0.125 A |
| operational current · with 2 current paths in series at DC-3 at DC-5 · at 24 V rated value | 300 A |
| operational current · with 3 current paths in series at DC-3 at DC-5 · at 24 V rated value | 300 A |
| operating power · at AC-3 · at 230 V rated value | 75 kW |
| operating power · at AC-3 · at 500 V rated value | 160 kW |
| operating power · at AC-3 · at 690 V rated value | 250 kW |
| operating power · at AC-3 · at 1000 V rated value | 132 kW |
| operating power · at AC-3e · at 230 V rated value | 75 kW |
| operating power · at AC-3e · at 400 V rated value | 132 kW |
| operating power · at AC-3e · at 500 V rated value | 160 kW |
| operating power · at AC-3e · at 690 V rated value | 250 kW |
| operating power · at AC-3e · at 1000 V rated value | 132 kW |
| operating power for approx. 200000 operating cycles at AC-4 · at 400 V rated value | 66 kW |
| operating apparent power at AC-6a · up to 230 V for current peak value n=20 rated value | 100 kVA |
| operating apparent power at AC-6a · up to 400 V for current peak value n=20 rated value | 180 kVA |
| operating apparent power at AC-6a · up to 500 V for current peak value n=20 rated value | 220 kVA |
| operating apparent power at AC-6a · up to 690 V for current peak value n=20 rated value | 310 kVA |
| operating apparent power at AC-6a · up to 1000 V for current peak value n=20 rated value | 160 kVA |
| short-time withstand current in cold operating state up to 40 °C · limited to 1 s switching at zero current maximum | 4 880 A; Use minimum cross-section acc. to AC-1 rated value |
| no-load switching frequency · at AC | 2 000 1/h |
| no-load switching frequency · at DC | 2 000 1/h |
| operating frequency · at AC-1 maximum | 800 1/h |
| operating frequency · at AC-2 maximum | 250 1/h |
| operating frequency · at AC-3e · maximum | 500 1/h |
| operating frequency · at AC-4 maximum | 130 1/h |
| control supply voltage at DC rated value | 220 ... 240 V |
| operating range factor control supply voltage rated value of magnet coil at DC · initial value | 0.8 |
| apparent pick-up power · at minimum rated control supply voltage at AC · at 50 Hz | 490 V·A |
| apparent pick-up power · at maximum rated control supply voltage at AC · at 60 Hz | 590 V·A |
| apparent pick-up power of magnet coil at AC · at 50 Hz | 590 V·A |
| apparent pick-up power of magnet coil at AC · at 60 Hz | 590 V·A |
| inductive power factor with closing power of the coil · at 50 Hz | 0.9 |
| inductive power factor with closing power of the coil · at 60 Hz | 0.9 |
| apparent holding power · at minimum rated control supply voltage at DC | 6.1 V·A |
| apparent holding power · at maximum rated control supply voltage at DC | 7.4 V·A |
| inductive power factor with the holding power of the coil · at 50 Hz | 0.9 |
| closing power of magnet coil at DC | 650 W |
| closing delay · at AC | 30 ... 95 ms |
| closing delay · at DC | 30 ... 95 ms |
| opening delay · at AC | 40 ... 80 ms |
| opening delay · at DC | 40 ... 80 ms |
| arcing time | 10 ... 15 ms |
| control version of the switch operating mechanism | Standard A1 - A2 |
| operational current at AC-12 maximum | 10 A |
| operational current at AC-15 · at 230 V rated value | 6 A |
| operational current at AC-15 · at 400 V rated value | 3 A |
| operational current at AC-15 · at 500 V rated value | 2 A |
| operational current at AC-15 · at 690 V rated value | 1 A |
| operational current at DC-12 · at 24 V rated value | 10 A |
| operational current at DC-12 · at 48 V rated value | 6 A |
| operational current at DC-12 · at 60 V rated value | 6 A |
| operational current at DC-12 · at 110 V rated value | 3 A |
| operational current at DC-12 · at 125 V rated value | 2 A |
| operational current at DC-12 · at 220 V rated value | 1 A |
| operational current at DC-12 · at 600 V rated value | 0.15 A |
| operational current at DC-13 · at 24 V rated value | 10 A |
| operational current at DC-13 · at 48 V rated value | 2 A |
| operational current at DC-13 · at 60 V rated value | 2 A |
| operational current at DC-13 · at 110 V rated value | 1 A |
| operational current at DC-13 · at 125 V rated value | 0.9 A |
| operational current at DC-13 · at 220 V rated value | 0.3 A |
| operational current at DC-13 · at 600 V rated value | 0.1 A |
| contact reliability of auxiliary contacts | 1 faulty switching per 100 million (17 V, 1 mA) |
| full-load current (FLA) for 3-phase AC motor · at 600 V rated value | 242 A |
| yielded mechanical performance [hp] · for 3-phase AC motor · at 200/208 V rated value | 75 hp |
| yielded mechanical performance [hp] · for 3-phase AC motor · at 220/230 V rated value | 100 hp |
| yielded mechanical performance [hp] · for 3-phase AC motor · at 460/480 V rated value | 200 hp |
| yielded mechanical performance [hp] · for 3-phase AC motor · at 575/600 V rated value | 250 hp |
| contact rating of auxiliary contacts according to UL | A600 / Q600 |
| design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 V | C characteristic: 10 A; 0.4 kA |
| design of the fuse link · for short-circuit protection of the main circuit · with type of coordination 1 required | gG: 500 A (690 V, 100 kA) |
| mounting position | with vertical mounting surface +/-90° rotatable, with vertical mounting surface +/- 22.5° tiltable to the front and back |
| fastening method side-by-side mounting | Yes |
| required spacing · with side-by-side mounting · forwards | 20 mm |
| required spacing · with side-by-side mounting · upwards | 10 mm |
| required spacing · with side-by-side mounting · downwards | 10 mm |
| required spacing · with side-by-side mounting · at the side | 0 mm |
| required spacing · for grounded parts · forwards | 20 mm |
| required spacing · for grounded parts · upwards | 10 mm |
| required spacing · for grounded parts · at the side | 10 mm |
| required spacing · for grounded parts · downwards | 10 mm |
| required spacing · for live parts · forwards | 20 mm |
| required spacing · for live parts · upwards | 10 mm |
| required spacing · for live parts · downwards | 10 mm |
| required spacing · for live parts · at the side | 10 mm |
| type of electrical connection · for auxiliary and control circuit | screw-type terminals |
| type of electrical connection · at contactor for auxiliary contacts | Screw-type terminals |
| type of electrical connection · of magnet coil | screw terminal |
| width of connection bar | 25 mm |
| thickness of connection bar | 6 mm |
| diameter of holes | 11 mm |
| number of holes | 1 |
| type of connectable conductor cross-sections · for AWG cables for main contacts | 2/0 ... 500 kcmil |
| connectable conductor cross-section for main contacts · stranded | 70 ... 240 mm2 |
| connectable conductor cross-section for auxiliary contacts · solid or stranded | 0.5 ... 4 mm2 |
| connectable conductor cross-section for auxiliary contacts · finely stranded with core end processing | 0.5 ... 2.5 mm2 |
| type of connectable conductor cross-sections · for auxiliary contacts · solid | 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2), max. 2x (0.75 ... 4 mm2) |
| AWG number as coded connectable conductor cross section for auxiliary contacts | 18 ... 14 |
| product function · mirror contact according to IEC 60947-4-1 | Yes |
| product function · positively driven operation according to IEC 60947-5-1 | No |
| product function · suitable for safety function | Yes |
| suitability for use safety-related switching OFF | Yes |
| service life maximum | 20 a |
| test wear-related service life necessary | Yes |
| proportion of dangerous failures · with low demand rate according to SN 31920 | 40 % |
| proportion of dangerous failures · with high demand rate according to SN 31920 | 73 % |
| B10 value with high demand rate according to SN 31920 | 1 000 000 |
| failure rate [FIT] with low demand rate according to SN 31920 | 100 FIT |
| device type according to ISO 13849-1 | 3 |
| overdimensioning according to ISO 13849-2 necessary | Yes |
| safety device type according to IEC 61508-2 | Type A |
| touch protection on the front according to IEC 60529 | finger-safe, for vertical contact from the front with box terminal/cover |
| Environmental Product Declaration · global warming potential [CO2 eq] / during manufacturing | 31.5 kg |
Source: manufacturer data · Last verified: 03 Nov 2026
No documents are on file for this part yet.
Ask us for the datasheetThe rated current of 3RT1065-6AP36 is 265 A (AC-3, 400 V).
The rated operational voltage of 3RT1065-6AP36 is 1000 V AC.
The rated motor power of 3RT1065-6AP36 is 132 kW (AC-3, 400 V).
The control voltage range of 3RT1065-6AP36 is 220–240 V AC/DC.
The EAN (GTIN) of 3RT1065-6AP36 is 4011209507937.
3RT1065-6AP36 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1 business day.
AC-1 and AC-6a contactors for data center PDU and UPS systems: sizing, harmonic derating, coil selection, and endurance guidance for engineers. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Master AC3 rating selection with our complete contactor checklist covering load sizing, utilization categories, derating, and coordination. Shop at Stoklink.