Part number
3RT1055-6AP36
1,765.98 SR In stock · 50+ Dispatch Planned dispatch date. We aim to ship within 1 business day. Depending on warehouse workload it can take 2–3 business days. · From Türkiye

Siemens 3RT1055-6AP36 3RT1 150A 3P 400V Contactor

The Siemens 3RT1055-6AP36 is a 3-pole SIRIUS 3RT1 contactor rated 150 A (AC-3) / 75 kW at 400 V, 125 hp at 480 V, with a 220–240 V AC/DC coil and 2 NO + 2 NC auxiliary contacts.

Poles
3
AC-3 current (400 V)
150 A
Motor power (400 V)
75 kW
Motor power (480 V)
125 hp @ 460/480 V
Coil voltage
220–240 V AC/DC
Auxiliary contacts
2 NO + 2 NC
EAN
4011209507333
Description

About the 3RT1055-6AP36

The Siemens 3RT1055-6AP36 is a contactor from the SENTRON/SIRIUS 3RT1 series. Power contactor, AC-3e/AC-3 150 A, 75 kW / 400 V AC (50-60 Hz) / DC Uc: 220-240 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional main circuit: busbar control and auxiliary circuit: screw terminal. Supplied by Stoklink for industrial and commercial low-voltage applications.

Applications & Use Cases

The Siemens 3RT1055-6AP36 is used in industrial control panels, distribution boards and automation systems. As part of the Siemens 3RT1 range it integrates with compatible SENTRON/SIRIUS components for a coordinated low-voltage installation. Genuine Siemens product supplied by Stoklink with fast dispatch from Türkiye.

Specification

Full specification

183 values · Last verified 28 Oct 2026

General 4

Series SIRIUS 3RT1
Contactor size / frame S6
Number of poles 3
Main contact configuration 3 NO

Electrical 8

Rated operational current Ie, AC-3, 400 V 150 A
Rated motor power, AC-3, 400 V 75 kW
Rated operational current, AC-1 (60 °C) 160 A
Rated operational current, AC-1 (40 °C) 185 A
Rated operational current, AC-4, 400 V 132 A
Max. rated operational voltage Ue 1000 V
Rated insulation voltage Ui 1000 V
Rated impulse withstand voltage Uimp 8 kV

Control circuit 5

Rated control supply voltage Uc 220–240 V
Coil type AC-DC
Coil frequency 50/60 Hz
Coil technology Conventional, surge suppressor with varistor
Coil holding power 5.2 W | VA
Show all 53 specifications ↓ Show less ↑36 more values in Identification, Auxiliary contacts, Mechanical, Dimensions and weight, Environmental, North American ratings (UL/CSA), Certifications and standards, Logistics. 130 more as published by Siemens are shown on request.

Identification 14

Part number 3RT1055-6AP36
Model code S6
Brand Siemens
Series SIRIUS 3RT1
Family Contactors
Condition New, factory sealed
Source Siemens and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 4011209507333
ETIM class EC000066
eCl@ss 27371003
UPC 754554771670
UNSPSC 39121529

Auxiliary contacts 4

Built-in auxiliary contacts, NO 2
Built-in auxiliary contacts, NC 2
Auxiliary contacts 2 NO + 2 NC
Mirror contact (IEC 60947-4-1 Annex F) Yes

Mechanical 2

Main circuit connection Busbar
Mounting Panel (screw) mounting

Dimensions and weight 4

Width 120 mm
Height 172 mm
Depth 170 mm
Net weight 3.205 kg

Environmental 4

Ambient operating temperature -25 … 60 °C
Degree of protection IP00; IP20 with box terminal/cover
Mechanical durability 10000000 cycles
Max. operating frequency, AC-3 750 cycles/h

North American ratings (UL/CSA) 2

Motor rating (UL/CSA) 50 hp @ 200/208 V · 60 hp @ 220/230 V · 125 hp @ 460/480 V · 150 hp @ 575/600 V · 30 hp @ 230 V (1-ph)
Full-load amps @ 480 V 156 A

Certifications and standards 1

Certifications Marine, UL

Logistics 5

Package dimensions (L × W × H) 196 × 131 × 183 mm
Shipping weight 3.32 kg
Ships from Türkiye
Dispatch 16 Nov
Stock In stock
Additional manufacturer data 130 130 more values as published by Siemens, shown on request.

Additional manufacturer data 130

product brand name SIRIUS
product designation Power contactor
product extension · function module for communication No
product extension · auxiliary switch Yes
power loss [W] for rated value of the current · at AC in hot operating state 27 W
power loss [W] for rated value of the current · without load current share typical 5.2 W
type of calculation of power loss current-dependent quadratic
insulation voltage · of auxiliary circuit with degree of pollution 3 rated value 500 V
surge voltage resistance · of auxiliary circuit rated value 6 kV
maximum permissible voltage for protective separation between coil and main contacts according to EN 60947-1 690 V
shock resistance at rectangular impulse · at AC 8,5 g / 5 ms, 4,2 g / 10 ms
shock resistance at rectangular impulse · at DC 8,5 g / 5 ms, 4,2 g / 10 ms
shock resistance with sine pulse · at AC 13,4 g / 5 ms, 6,5 g / 10 ms
shock resistance with sine pulse · at DC 13,4 g / 5 ms, 6,5 g / 10 ms
mechanical service life (operating cycles) · of the contactor with added electronically optimized auxiliary switch block typical 5 000 000
reference code according to IEC 81346-2 Q
Substance Prohibitance (day/month/year) 05/01/2012
SVHC substance name Lead CAS-No. 7439-92-1
installation altitude at height above sea level maximum 2 000 m
ambient temperature · during storage -55 ... +80 °C
relative humidity minimum 10 %
relative humidity at 55 °C according to IEC 60068-2-30 maximum 95 %
number of NC contacts for main contacts 0
operating voltage · at AC-3e rated value maximum 1 000 V
operational current · at AC-1 · up to 690 V at ambient temperature 40 °C rated value 185 A
operational current · at AC-1 · up to 1000 V at ambient temperature 60 °C rated value 90 A
operational current · at AC-3 · at 500 V rated value 150 A
operational current · at AC-3 · at 690 V rated value 150 A
operational current · at AC-3 · at 1000 V rated value 65 A
operational current · at AC-3e · at 400 V rated value 150 A
operational current · at AC-3e · at 500 V rated value 150 A
operational current · at AC-3e · at 690 V rated value 150 A
operational current · at AC-3e · at 1000 V rated value 65 A
operational current · at AC-5a up to 690 V rated value 162 A
operational current · at AC-5b up to 400 V rated value 124 A
operational current · at AC-6a · up to 230 V for current peak value n=20 rated value 150 A
operational current · at AC-6a · up to 400 V for current peak value n=20 rated value 150 A
operational current · at AC-6a · up to 500 V for current peak value n=20 rated value 150 A
operational current · at AC-6a · up to 690 V for current peak value n=20 rated value 150 A
operational current · at AC-6a · up to 1000 V for current peak value n=20 rated value 65 A
minimum cross-section in main circuit at maximum AC-1 rated value 95 mm2
operational current for approx. 200000 operating cycles at AC-4 · at 400 V rated value 68 A
operational current · up to 400 V for current peak value n=20 rated value 100 kVA
operational current · up to 500 V for current peak value n=20 rated value 130 kVA
operational current · up to 690 V for current peak value n=20 rated value 170 kVA
operational current · up to 1000 V for current peak value n=20 rated value 110 kVA
operating apparent power at AC-6a · up to 230 V for current peak value n=30 rated value 40 kVA
operating apparent power at AC-6a · up to 400 V for current peak value n=30 rated value 70 kVA
operating apparent power at AC-6a · up to 500 V for current peak value n=30 rated value 90 kVA
operating apparent power at AC-6a · up to 690 V for current peak value n=30 rated value 120 kVA
operating apparent power at AC-6a · up to 1000 V for current peak value n=30 rated value 110 kVA
short-time withstand current in cold operating state up to 40 °C · limited to 1 s switching at zero current maximum 2 727 A; Use minimum cross-section acc. to AC-1 rated value
no-load switching frequency · at AC 2 000 1/h
no-load switching frequency · at DC 2 000 1/h
operating frequency · at AC-1 maximum 800 1/h
operating frequency · at AC-2 maximum 300 1/h
operating frequency · at AC-3e · maximum 750 1/h
operating frequency · at AC-4 maximum 130 1/h
control supply voltage at DC rated value 220 ... 240 V
operating range factor control supply voltage rated value of magnet coil at DC · initial value 0.8
apparent pick-up power · at minimum rated control supply voltage at AC · at 50 Hz 250 V-A
apparent pick-up power · at maximum rated control supply voltage at AC · at 60 Hz 300 V-A
apparent pick-up power of magnet coil at AC · at 50 Hz 300 V-A
apparent pick-up power of magnet coil at AC · at 60 Hz 300 V-A
inductive power factor with closing power of the coil · at 50 Hz 0.9
inductive power factor with closing power of the coil · at 60 Hz 0.9
apparent holding power · at minimum rated control supply voltage at DC 4.3 V-A
apparent holding power · at maximum rated control supply voltage at DC 5.2 V-A
inductive power factor with the holding power of the coil · at 50 Hz 0.8
closing power of magnet coil at DC 360 W
closing delay · at AC 20 ... 95 ms
closing delay · at DC 20 ... 95 ms
opening delay · at AC 40 ... 60 ms
opening delay · at DC 40 ... 60 ms
arcing time 10 ... 15 ms
control version of the switch operating mechanism Standard A1 - A2
operational current at AC-12 maximum 10 A
operational current at AC-15 · at 230 V rated value 6 A
operational current at AC-15 · at 400 V rated value 3 A
operational current at AC-15 · at 500 V rated value 2 A
operational current at AC-15 · at 690 V rated value 1 A
operational current at DC-12 · at 24 V rated value 10 A
operational current at DC-12 · at 48 V rated value 6 A
operational current at DC-12 · at 60 V rated value 6 A
operational current at DC-12 · at 110 V rated value 3 A
operational current at DC-12 · at 125 V rated value 2 A
operational current at DC-12 · at 220 V rated value 1 A
operational current at DC-12 · at 600 V rated value 0.15 A
operational current at DC-13 · at 24 V rated value 10 A
operational current at DC-13 · at 48 V rated value 2 A
operational current at DC-13 · at 60 V rated value 2 A
operational current at DC-13 · at 110 V rated value 1 A
operational current at DC-13 · at 125 V rated value 0.9 A
operational current at DC-13 · at 220 V rated value 0.3 A
operational current at DC-13 · at 600 V rated value 0.1 A
contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
full-load current (FLA) for 3-phase AC motor · at 600 V rated value 144 A
yielded mechanical performance [hp] · for single-phase AC motor · at 230 V rated value 30 hp
yielded mechanical performance [hp] · for 3-phase AC motor · at 200/208 V rated value 50 hp
yielded mechanical performance [hp] · for 3-phase AC motor · at 220/230 V rated value 60 hp
yielded mechanical performance [hp] · for 3-phase AC motor · at 460/480 V rated value 125 hp
yielded mechanical performance [hp] · for 3-phase AC motor · at 575/600 V rated value 150 hp
contact rating of auxiliary contacts according to UL A600 / Q600
design of the miniature circuit breaker for short-circuit protection of the auxiliary circuit up to 230 V C characteristic: 10 A; 0.4 kA
design of the fuse link • for short-circuit protection of the main circuit — with type of coordination 1 required — with type of coordination 2 required • for short-circuit protection of the auxiliary switch required gG: 355 A (690 V, 100 kA) gG: 315 A (690 V, 100 kA), aM: 200 A (690 V, 50 kA), BS88: 315 A (415 V, 50 kA) gG: 10 A (500 V, 1 kA)
mounting position with vertical mounting surface ± 90° rotatable, with vertical mounting surface ± 22.5° tiltable to the front and back
fastening method side-by-side mounting Yes
required spacing • with side-by-side mounting — forwards — upwards — downwards — at the side • for grounded parts — forwards — upwards — at the side — for live parts — forwards — upwards — upwards — at the side 20 mm 10 mm 10 mm 0 mm 20 mm 10 mm 10 mm 20 mm 10 mm 10 mm
type of electrical connection • for main current circuit • for auxiliary and control circuit • at contactor for auxiliary contacts • of magnet coil Connection bar screw-type terminals Screw-type terminals screw terminal
width of connection bar 17 mm
thickness of connection bar 3 mm
diameter of holes 9 mm
number of holes 1
type of connectable conductor cross-sections • for AWG cables for main contacts 4 ... 250 kcmil
connectable conductor cross-section for main contacts • stranded 25 ... 120 mm2
connectable conductor cross-section for auxiliary contacts • solid or stranded • finely stranded with core end processing 0.5 ... 4 mm2 0.5 ... 2.5 mm2
type of connectable conductor cross-sections • for auxiliary contacts — solid — solid or stranded — finely stranded with core end processing 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2), max. 2x (0.75 ... 4 mm2) 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2), max. 2x (0.75 ... 4 mm2) 2x (0.5 ... 1.5 mm2), 2x (0.75 ... 2.5 mm2) 2x (20 ... 16), 2x (18 ... 14), 1x 12
AWG number as coded connectable conductor cross section for auxiliary contacts 18 ... 14
product function · mirror contact according to IEC 60947-4-1 • positively driven operation according to IEC 60947-5-1 • suitable for safety function Yes No
suitability for use safety-related switching OFF Yes
service life maximum 20 a
test wear-related service life necessary Yes
proportion of dangerous failures • with low demand rate according to SN 31920 • with high demand rate according to SN 31920 40 % 73 %
B10 value with high demand rate according to SN 31920 1 000 000
failure rate [FIT] with low demand rate according to SN 31920 100 FIT
device type according to ISO 13849-1 3
overdimensioning according to ISO 13849-2 necessary Yes
safety device type according to IEC 61508-2 Type A
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front with box terminal/cover
Environmental Product Declaration · global warming potential [CO2 eq] / during manufacturing • global warming potential [CO2 eq] / during sales • global warming potential [CO2 eq] / during operation • global warming potential [CO2 eq] / after end of life • global warming potential [CO2 eq] / total 17 kg 0.901 kg 363 kg -2.28 kg 379 kg

Source: manufacturer data · Last verified: 28 Oct 2026

Documents

Documents for 3RT1055-6AP36 6

Certifications

Certifications and standards

  • Marine
  • UL
Quick answers

Questions about the 3RT1055-6AP36

What is the rated current of 3RT1055-6AP36?

The rated current of 3RT1055-6AP36 is 150 A (AC-3, 400 V).

Which supply voltage is 3RT1055-6AP36 rated for?

The rated operational voltage of 3RT1055-6AP36 is 1000 V AC.

What motor power is 3RT1055-6AP36 rated for?

The rated motor power of 3RT1055-6AP36 is 75 kW (AC-3, 400 V).

Which control voltage does 3RT1055-6AP36 need?

The control voltage range of 3RT1055-6AP36 is 220–240 V AC/DC.

What is the EAN of 3RT1055-6AP36?

The EAN (GTIN) of 3RT1055-6AP36 is 4011209507333.

Where does 3RT1055-6AP36 ship from, and how fast?

3RT1055-6AP36 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1 business day.

Guides

Guides for contactors

All guides for contactors
Reviews

Customer reviews

Series

Siemens SIRIUS 3RT1

Brand
Siemens
Series
SIRIUS 3RT1
Series page →
Series

Other series in Contactors

1,765.98 SR In stock · 16 Nov
Quote

Get a Quote

Genuine parts

Genuine, factory-sealed parts

Siemens · 3RT1055-6AP36

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Siemens and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart

View cart