Part number
LC1D65ABD
877.00 SR In stock · 50+ Dispatch Planned dispatch date. We aim to ship within 1 business day. Depending on warehouse workload it can take 2–3 business days. · From Türkiye
Manufacturer phase-out

Schneider Electric has announced the end of LC1D65ABD

Last orders until 31 Dec 2026. After that date, supply depends on remaining stock. Date announced by Schneider Electric for Türkiye, where we source this part.

No replacement announced yet. Tell us the application and we will propose an alternative.

Schneider Electric LC1D65ABD TeSys Deca 3-Pole 65A 24VDC Coil 40HP 480V AC Contactor

The Schneider Electric LC1D65ABD is a 3-pole TeSys Deca Advanced contactor rated 65 A (AC-3) / 30 kW at 400 V, 40 hp at 480 V, with a 24 V DC coil and 1 NO + 1 NC auxiliary contacts.

Poles
3
AC-3 current (400 V)
65 A
Motor power (400 V)
30 kW
Motor power (480 V)
40 hp @ 460/480 V
Coil voltage
24 V DC
Auxiliary contacts
1 NO + 1 NC
EAN
3389119409094
Description

About the LC1D65ABD

The Schneider Electric LC1D65ABD is a TeSys Deca series 3-pole AC contactor rated at 65A and 40HP at 480V AC, designed for reliable motor switching and control in industrial applications. Featuring a 24VDC coil and a 100 kA SCCR (Short-Circuit Current Rating), the LC1D65ABD delivers robust performance in demanding environments. Weighing just 0.935 kg, this compact contactor is well-suited for panel builders and OEMs seeking proven motor starter solutions.

Applications & Use Cases

  • Motor Control: Ideal for starting and stopping AC induction motors up to 40HP in industrial machinery and HVAC systems.
  • Motor Starter Assemblies: Used in combination with thermal overload relays to form full motor starters for pumps, fans, and compressors.
  • Panel Building: Compact form factor suits MCC (Motor Control Centre) and control panel integration.
  • OEM Machinery: Suitable for original equipment manufacturers requiring reliable, high-cycle switching components.
  • Process Automation: Compatible with PLC-driven control systems operating on 24VDC logic circuits.

Applications (manufacturer): Motor control, Resistive load

Specification

Full specification

120 values · Last verified 03 Nov 2026

General 5

Series TeSys Deca Advanced
Contactor size / frame D65
Number of poles 3
Main contact configuration 3 NO
Utilisation categories AC-3 AC-3e AC-1 AC-4

Electrical 9

Rated operational current Ie, AC-3, 400 V 65 A
Rated motor power, AC-3, 400 V 30 kW
Motor power at other voltages, AC-3 18.5 kW @ 220/230 V · 37 kW @ 500 V · 37 kW @ 660/690 V
Rated operational current, AC-1 (60 °C) 80 A
Conventional free-air thermal current Ith 80 A
Rated motor power, AC-4, 400 V 11 kW
Max. rated operational voltage Ue 690 V
Rated insulation voltage Ui 690 V
Rated impulse withstand voltage Uimp 6 kV

Control circuit 4

Rated control supply voltage Uc 24 V
Coil type DC
Coil technology Built-in bidirectional peak limiting diode suppressor
Coil holding power 7.4 W | VA
Show all 55 specifications ↓ Show less ↑37 more values in Identification, Auxiliary contacts, Mechanical, Dimensions and weight, Environmental, North American ratings (UL/CSA), Certifications and standards, Logistics. 65 more as published by Schneider Electric are shown on request.

Identification 12

Part number LC1D65ABD
Model code D65
Brand Schneider Electric
Series TeSys Deca Advanced
Family Contactors
Condition New, factory sealed
Source Schneider Electric and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Phase-out announced by the manufacturer
Last order date 31 Dec 2026 · as announced for Türkiye, our sourcing market
EAN 3389119409094
Catalogue number explained LC1 = 3-pole contactor; D = TeSys Deca Advanced range; 65 = 65 A AC-3 rating; ABD = coil code (24 V DC)

Auxiliary contacts 4

Built-in auxiliary contacts, NO 1
Built-in auxiliary contacts, NC 1
Auxiliary contacts 1 NO + 1 NC
Mirror contact (IEC 60947-4-1 Annex F) Yes

Mechanical 2

Main circuit connection Screw terminal
Mounting 35 mm DIN rail, Panel (screw) mounting

Dimensions and weight 4

Width 55 mm
Height 122 mm
Depth 120 mm
Net weight 0.935 kg

Environmental 4

Ambient operating temperature -40 … 60 °C
Degree of protection IP20
Mechanical durability 10000000 cycles
Max. operating frequency, AC-3 3600 cycles/h

North American ratings (UL/CSA) 3

Motor rating (UL/CSA) 20 hp @ 200/208 V · 20 hp @ 230/240 V · 40 hp @ 460/480 V · 50 hp @ 575/600 V · 5 hp @ 115 V (1-ph) · 10 hp @ 230/240 V (1-ph)
Short-circuit current rating (SCCR) 100 kA
Max. operating voltage UL/CSA 600 V

Certifications and standards 2

Certifications CB Scheme, UL, CSA, CCC, CE, UKCA, EAC, Marine
Conforming standards CSA C22.2 No 14, EN 60947-4-1, EN 60947-5-1, IEC 60335-1, IEC 60335-2-40, IEC 60947-4-1, IEC 60947-5-1, UL 60335-2-40, UL 60947-4-1

Logistics 6

Package dimensions (L × W × H) 152 × 135 × 62 mm
Package weight 0.984 kg
Shipping weight 0.935 kg
Ships from Türkiye
Dispatch 16 Nov
Stock In stock
Additional manufacturer data 65 65 more values as published by Schneider Electric, shown on request.

Additional manufacturer data 65

Range TeSys TeSys Deca
Product or Component Type Contactor
Device short name LC1D
Compatibility code LC1D
Protective cover With
Irms rated making capacity 140 A AC for signalling circuit conforming to IEC 60947-5-1 250 A DC for signalling circuit conforming to IEC 60947-5-1 1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity 1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current 640 A 104 °F (40 °C) - 10 s for power circuit 900 A 104 °F (40 °C) - 1 s for power circuit 110 A 104 °F (40 °C) - 10 min for power circuit 260 A 104 °F (40 °C) - 1 min for power circuit 100 A - 1 s for signalling circuit 120 A - 500 ms for signalling circuit 140 A - 100 ms for signalling circuit
Associated fuse rating 10 A gG for signalling circuit conforming to IEC 60947-5-1 125 A gG at <= 690 V coordination type 1 for power circuit 125 A gG at <= 690 V coordination type 2 for power circuit
Average impedance 1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole 9.6 W AC-1 6.3 W AC-3 6.3 W AC-3e
Overvoltage category III
Pollution degree 3
Safety reliability level B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Electrical durability 0.5 Mcycles 80 A AC-1 <= 440 V 1.45 Mcycles 65 A AC-3 <= 440 V 1.45 Mcycles 65 A AC-3e <= 440 V
Control circuit type DC standard
Control circuit voltage limits 0.1...0.3 Uc (-40...158 °F (-40...70 °C)):drop-out DC 0.75...1.25 Uc (-40...140 °F (-40...60 °C)):operational DC 1...1.25 Uc (140...158 °F (60...70 °C)):operational DC
Inrush power in W 19 W 68 °F (20 °C))
Operating time 50 ±15 % ms closing 16...24 ms opening
Time constant 34 ms
Tightening torque Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors flat Ø 6 mm Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors Philips No 2 Power circuit 70.8 lbf.in (8 N.m) EverLink BTR screw connectors 0.04...0.05 in2 (25...35 mm2) hexagonal 0.2 in (4 mm) Power circuit 44.3 lbf.in (5 N.m) EverLink BTR screw connectors 0.002...0.04 in2 (1...25 mm2) hexagonal 0.2 in (4 mm) Control circuit 15.05 lbf.in (1.7 N.m) EverLink BTR screw connectors pozidriv No 2 Power circuit 22.1 lbf.in (2.5 N.m) EverLink BTR screw connectors pozidriv No 2
Signalling circuit frequency 25...400 Hz
Minimum switching voltage 17 V for signalling circuit
Minimum switching current 5 mA for signalling circuit
Insulation resistance > 10 MOhm for signalling circuit
Non-overlap time 1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
Protective treatment THIEC 60068-2-30
Climatic withstand IACS E10 exposure to damp heat IEC 60947-1 Annex Q category D exposure to damp heat
Operating altitude 0...9842.52 ft (0...3000 m)
Fire resistance 1562 °F (850 °C) IEC 60695-2-1
Mechanical robustness Vibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor closed 15 Gn for 11 ms) Shocks contactor open 10 Gn for 11 ms)
Category US1CTR121254
Discount Schedule CTR1
Returnability Yes
Unit Type of Package 1 PCE
Nbr. of units in pkg. 1
Unit Type of Package 2 S02
Number of Units in Package 2 10
Package 2 Height 5.9 in (15 cm)
Package 2 Width 11.8 in (30 cm)
Package 2 Length 15.7 in (40 cm)
Package 2 Weight 22.906 lb(US) (10.390 kg)
Unit Type of Package 3 P06
Number of Units in Package 3 160
Package 3 Height 30.315 in (77.000 cm)
Package 3 Width 31.496 in (80.000 cm)
Package 3 Length 23.622 in (60.000 cm)
Package 3 Weight 385.236 lb(US) (174.740 kg)
Total lifecycle Carbon footprint 87 kg CO2 eq.
Carbon footprint of the manufacturing phase [A1 to A3] 5 kg CO2 eq.
Carbon footprint of the distribution phase [A4] 0.4 kg CO2 eq.
Carbon footprint of the installation phase [A5] 0.1 kg CO2 eq.
Carbon footprint of the use phase [B2, B3, B4, B6] 80 kg CO2 eq.
Carbon footprint of the end-of-life phase [C1 to C4] 1 kg CO2 eq.
Environmental Disclosure Product Environmental Profile
Packaging made with recycled cardboard Yes
Packaging without single use plastic Yes
California proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide &amp Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
POP Directive No POPs
PVC free Yes
Repair No
Recyclability potential, in % 62
Circularity Profile End of Life Information
Take-back No
WEEE Label The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.

Source: manufacturer data · Last verified: 03 Nov 2026

Documents

Documents for LC1D65ABD

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • CB Scheme
  • UL
  • CSA
  • CCC
  • CE
  • UKCA
  • EAC
  • Marine
  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60335-1
  • IEC 60335-2-40
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 60335-2-40
  • UL 60947-4-1
Quick answers

Questions about the LC1D65ABD

What is the rated current of LC1D65ABD?

The rated current of LC1D65ABD is 65 A (AC-3, 400 V).

Which supply voltage is LC1D65ABD rated for?

The rated operational voltage of LC1D65ABD is 690 V AC.

What motor power is LC1D65ABD rated for?

The rated motor power of LC1D65ABD is 30 kW (AC-3, 400 V).

Which control voltage does LC1D65ABD need?

The control voltage range of LC1D65ABD is 24 V DC.

What is the EAN of LC1D65ABD?

The EAN (GTIN) of LC1D65ABD is 3389119409094.

Where does LC1D65ABD ship from, and how fast?

LC1D65ABD ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival. Stock items are dispatched within 1 business day.

Guides

Guides for contactors

All guides for contactors
Reviews

Customer reviews

Series

Schneider Electric TeSys Deca Advanced

Brand
Schneider Electric
Series
TeSys Deca Advanced
Series page →
Series

Other series in Contactors

877.00 SR In stock · 16 Nov
Quote

Get a Quote

Genuine parts

Genuine, factory-sealed parts

Schneider Electric · LC1D65ABD

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Schneider Electric and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart