IEC 60947-4-1 Standards for Contactors and Motor Starters Explained
Master AC-3 rating selection under IEC 60947-4-1 for contactors and motor starters, including utilization categories and coordination types. Shop at Stoklink.
The Schneider Electric TPRVM001 is a TeSys Island voltage interface module that monitors the mains voltage supplying the island, measuring 100-690 V AC at 47-63 Hz. It reports RMS phase voltages, frequency and phase sequence to the TPRBC bus coupler for power and energy monitoring.
Add the TPRVM001 to a TeSys island configuration when the application needs mains-voltage monitoring (RMS value, dip/swell detection, phase sequence) alongside the motor starters, feeding the data back to the TPRBC bus coupler for power and energy calculation.
| Range | TeSys |
|---|---|
| Product name | TeSys island |
| Device short name | TPRVM |
| Product or Component Type | Voltage interface module |
| Device presentation | Monitoring of the mains voltage powering the island, Reporting of the voltage to the bus coupler to enable power & energy monitoring |
| Function of module | Monitoring of voltages in single phase systems L-N or L-L, Monitoring of voltages in 3-phase systems without neutral N connection, Calculation of RMS phase voltages, voltage phase sequence, fundamental frequency, Identification of dip and swell events level and duration |
| Product compatibility | TPRBC bus coupler |
| [Ue] rated operational voltage | 690 V AC 47...63 Hz |
| [Ui] rated insulation voltage | 690 V IEC 61010-1 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 61010-1 |
| Overvoltage category | III |
| Monitoring type | Phase voltage 100...690 V, Phase frequency 47...63 Hz, Phase sequence |
| Measurement accuracy | Voltage +/- 5 %,, Frequency +/- 1 Hz, |
| Local signalling | 1 LED (green/red) for DS (device status), 1 LED (green/red) for VS (voltage status) |
| [Us] rated supply voltage | 24 V DC supplied by the bus coupler |
|---|---|
| Current consumption | 2 mA |
| Power dissipation in W | 0.5 W maximum |
| Standards | IEC 61010-2-201, UL 61010-2-201, CSA C22.2 No 61010-2-201 |
| Product certifications | CSA, UL, EAC (pending) |
| Mounting mode | Horizontal and vertical 35 mm symmetrical rail) |
| Connections - terminals | Measuring input removable spring terminal block 3 0.0003…0.004 in² (0.2…2.5 mm²) 24 AWG...14 AWG)rigid, Measuring input removable spring terminal block 3 0.0003…0.004 in² (0.2…2.5 mm²) 24 AWG...14 AWG)flexible without cable end, Measuring input removable spring terminal block 3 0.0004…0.004 in² (0.25…2.5 mm²) 22 AWG...14 AWG)flexible with cable end |
| Width | 1.0 in (25 mm) |
| Height | 4.6 in (118 mm) |
| Depth | 4.5 in (114 mm) |
| Net Weight | 0.351 lb(US) (0.159 kg) |
| Ambient air temperature for storage | -13…158 °F (-25…70 °C) |
|---|---|
| Ambient Air Temperature for Operation | 14…140 °F (-10…60 °C) |
| Relative Humidity | 5…95 % |
| Operating altitude | 0...6561.68 ft (0...2000 m) without derating |
| IP degree of protection | IP20 |
| Pollution degree | 2 |
| Protective treatment | TC |
| Fire resistance | 1760 °F (960 °C) UL 94 |
| Shock resistance | 15 gn 11 ms) IEC 60068-2-27 |
| Vibration resistance | 1.5 mm peak to peak 3…13 Hz) IEC 60068-2-6, 1 gn 13…200 Hz) IEC 60068-2-6 |
| Electromagnetic compatibility | Electrostatic discharge, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2, Radiated RF fields, level 3, 10 V/m, conforming to EN/IEC 61000-4-3, Line voltage circuit: fast transients immunity test, level 3, 2 kV, conforming to EN/IEC 61000-4-4, Line voltage circuit: surge immunity test (common mode), level 3, 2 kV, conforming to EN/IEC 61000-4-5 |
| Part number | TPRVM001 |
|---|---|
| Type designation | TPRVM |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3606489832889 |
| Warranty (in months) | 18 |
|---|
| Country of origin | ID |
|---|---|
| Shipping weight | 0.159 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe tariff (HS) code on file for TPRVM is 853650.
The EAN (GTIN) of TPRVM is 3606489832889.
TPRVM ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Master AC-3 rating selection under IEC 60947-4-1 for contactors and motor starters, including utilization categories and coordination types. Shop at Stoklink.
Compare AC3 rating IEC contactors versus NEMA size codes, with cross-reference tables, derating formulas, and selection tips for engineers. Shop at Stoklink.
Size a contactor for a 3-phase motor using IEC 60947-4-1 methodology, AC-3 vs AC-4 categories, NEMA equivalents, and Type 2 coordination. Shop at Stoklink.