- Part number
- SSD1A335BDC1
- Model no
- SSD1
Schneider Electric SSD1A335BDC1 Harmony SSD1 35A 4-32V DC In 48-600V AC Out Solid State Relay
Harmony SSD1 DIN rail solid state relay, 35A, zero-voltage switching, 4-32V DC in, 48-600V AC out.
Description
About the SSD1
About the SSD1
The Schneider Electric SSD1A335BDC1 is a Harmony SSD1 DIN rail solid state relay rated 35 A with zero-voltage switching, a 4-32 V DC control input, and a 48-600 V AC load output. It mounts on 35 mm DIN rail, switches loads up to 7.46 kW/10 hp at 480 V AC, and carries a 600 V insulation rating.
Certifications & Standards
- UL
- CSA
- UL 508
- CSA C22.2 No 14-13
- IEC 61373 Class B category 1
- IEC 60947-4-3
- IEC 62314
- IEC 60950-1
Selection Notes
SSD1A335BDC1 covers motor loads up to 7.46 kW/10 hp at 480 V AC - roughly 3.3x the power handling of the 20 A SSD1 sibling in the same 22.5 mm DIN rail footprint, useful when panel space is fixed but load current scales up. Inrush current (1350 A at 60 Hz) is proportionally higher than the 20 A part's 300 A, so upstream short-circuit protection coordination (Type 1/Type 2) should be re-checked when stepping up from 20 A to 35 A. Same 4-32 V DC control input and 600 V insulation rating as the rest of the SSD1 zero-voltage-switching family.
Specification
Full specification
Main 9
| Range of Product | Harmony Solid State Relays |
|---|---|
| Product or Component Type | Modular DIN rail relay |
| Device short name | SSD1 |
| Number of Channels | 1 |
| Number of phases | 1 phase |
| Product configuration type | Relay configuration |
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
| rated current | 35 A |
| Output switching mode | Zero voltage switching |
Complementary 39
| operating frequency | 47...440 Hz |
|---|---|
| Rated duty | Uninterrupted |
| Output voltage | 48...600 V AC |
| control circuit voltage | 4...32 V DC |
| Tightening torque | 1.5...1.7 N.m for control input, 13...15 lb.in for control input, 1.5...1.7 N.m for load output, 13...15 lb.in for load output |
| Connections - terminals | screw terminals, clamping connection capacity:1...6 mm², 18 AWG...10 AWG for input, screw terminals, clamping connection capacity:1...6 mm², 18 AWG...10 AWG for output |
| Dielectric strength | 4 kV AC for input/output circuit, 4 kV AC for input or output to case |
| rated impulse withstand voltage | 6 kV for input/output circuit, 6 kV for input or output to case |
| Insulation resistance | 1000 MOhm at 500 V DC |
| Local signalling | LED (green) for control voltage |
| pick-up voltage | 4 V DC turn-on |
| drop-out voltage | 1 V DC turn-off |
| input current range | 5…15 mA |
| solid state switching type | Zero voltage switching |
| Load current | 0.2…35 A |
| transient overvoltage | 1200 V |
| Inrush current | 1200 A at 60 Hz |
| Maximum voltage drop | <1.3 V on-state |
| motor controller rating | 1.5 kW/2 hp at 120 V AC, 3.73 kW/5 hp at 240 V AC, 7.46 kW/10 hp at 480 V AC |
| Electromagnetic compatibility | Electrostatic discharge 6 kV criteria B contact discharge conforming to IEC 61000-4-2, Electrostatic discharge 8 kV criteria B air discharge conforming to IEC 61000-4-2, Conducted RF disturbances 10 V, 0.15...80 MHz criteria A level 3 conforming to IEC 61000-4-6, Electrical fast transient/burst immunity test 2 kV, 5/100 kHz criteria B output ports conforming to IEC 61000-4-4, Electrical fast transient/burst immunity test 1 kV, 5/100 kHz criteria B input ports conforming to IEC 61000-4-4, Radiated radio-frequency electromagnetic field immunity test 10 V/m, 80 MHz...1 GHz criteria A conforming to IEC 61000-4-3, Radiated radio-frequency electromagnetic field immunity test 3 V/m, 1.4...6 GHz criteria A conforming to IEC 61000-4-3, Surge immunity test 1 kV criteria B output ports line to line conforming to IEC 61000-4-5, Surge immunity test 2 kV criteria B output ports line to earth conforming to IEC 61000-4-5, Surge immunity test 1 kV criteria B input ports line to earth conforming to IEC 61000-4-5, Radiated emission environment A for DC input supply conforming to CISPR 11, Conducted emission environment A for DC input supply conforming to CISPR 11 |
| device form designation | Form 5 semiconductor output DOL contactor |
| Maximum I²t for fusing | 7200 A².s for 10 ms, 6588 A².s for 8.33 ms |
| Maximum leakage current | 1 mA off-state |
| DV/dt | 500 V/µs off-state at maximum rated voltage |
| Response time | 0.5 cycle (turn-on), 0.5 cycle (turn-off) |
| Power factor | 0.5 with maximum load |
| short circuit protection coordination | Type 1, Type 2 |
| Overvoltage category | III |
| Width | 0.9 in (22.5 mm) |
| Height | 3.7 in (95.0 mm) |
| Depth | 4.6 in (117.0 mm) |
| test button | Without test button |
| Net Weight | 0.7 lb(US) (0.3 kg) |
| Device presentation | Complete product |
| Protection device type | TVS |
| Load Category | LCA |
| Rated frequency (fr) | 47...440 Hz |
| Utilisation category | AC-51 35 A conforming to IEC 60947-4-3 |
| [Ui] Rated Insulation Voltage | 600 V |
Environment 8
| Flammability rating | V-0 conforming to UL 94 |
|---|---|
| Vibration resistance | 0.75 mm (f = 10…150 Hz) conforming to IEC 60068-2-6 |
| Shock resistance | 15 gn for 11 ms (peak acceleration) , longitudinal position conforming to IEC 60068-2-27, 15 gn for 11 ms (peak acceleration) , vertical position conforming to IEC 60068-2-27 |
| Pollution degree | 2 |
| Standards | IEC 60947-4-3, IEC 62314, CSA C22.2 No 14-18, UL 508 |
| IP degree of protection | IP20 |
| Ambient Air Temperature for Operation | -40…176 °F (-40…80 °C) |
| Ambient Air Temperature for Storage | -40…212 °F (-40…100 °C) |
Show all 70 specifications ↓ Show less ↑14 more values in Identification, Contractual warranty, Logistics.
Identification 8
| Part number | SSD1A335BDC1 |
|---|---|
| Type designation | SSD1 |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3606489807894 |
Contractual warranty 1
| Warranty (in months) | 18 |
|---|
Logistics 5
| Country of origin | CN |
|---|---|
| Shipping weight | 0.3 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
Documents
Documents for SSD1A335BDC1
No documents are on file for this part yet.
Ask us for the datasheet
Certifications
Certifications and standards
- IEC 60947-4-3
- IEC 62314
- CSA C22.2 No 14-18
- UL 508
Quick answers
Questions about the SSD1
What is the rated current of SSD1?
The rated current of SSD1 is 35 A.
What is the HS code of SSD1 for customs?
The tariff (HS) code on file for SSD1 is 85364900.
What is the EAN of SSD1?
The EAN (GTIN) of SSD1 is 3606489807894.
Where does SSD1 ship from, and how fast?
SSD1 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
Reviews
Customer reviews
Series
Schneider Electric Harmony Solid State Relays
- Brand
- Schneider Electric
- Series