Programmable Logic Controller Guide: Selection, Application, and Maintenance for Engineers
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
The Schneider Electric NTSDDO0802XK is a Modicon Edge I/O NTS discrete output module kit with 8 transistor outputs at 24 V DC, 500 mA per channel, pre-assembled on its NTSXBA0200H base. Channels wire in 1 or 2 wires with short-circuit and over-current protection, covering a -20...60 degC operating range. It mounts on a DIN rail and connects to Modicon M262 or M580 controllers.
The NTSDDO0802XK supports paralleling two channels for redundant control or doubled current, a useful option when a single 500 mA output is marginal for the load without stepping up to the 2 A-per-channel NTSDDO0802K. It shares its field power with the bus rather than requiring an external supply, simplifying wiring versus the externally-powered 0802K variant at the cost of lower total module current (4 A vs 8 A). Pick the 16-channel NTSDDO1602XK instead when the panel needs double the point density at the same 500 mA-per-channel rating.
| Range of Product | Modicon Edge I/O NTS |
|---|---|
| Product or Component Type | Discrete output module kit |
| Kit composition | NTSDDO0802X module, NTSXBA0200H base |
| Mandatory accessory | NTSXTB18_0_H terminal block |
| Product Compatibility | NTSN..... |
| Range Compatibility | Logic/motion controller - Modicon M262, Modicon M580, Third party |
| Device Application | Industrial Application |
| Discrete output number | 8 |
| Group of output channels | 1 group |
| Discrete output logic | Positive logic (source) |
| Discrete output voltage | 24 V DC |
| Operating Mode | Synchronous/Isochronous |
| Discrete output number | 8 transistor |
|---|---|
| Output wiring mode | 1 or 2 wires |
| Discrete output current | 0.5 A per channel, 4 A per module |
| Discrete output frequency | 1 kHz for resistive load, 0.5/LI² Hz for inductive load |
| Response time on output | 90 µs maximum (turn on), 110 µs maximum (turn off) |
| Maximum leakage current | 0.001 mA per channel |
| Maximum voltage drop | <0.1 V per channel DC |
| Maximum tungsten load | <12 W |
| Paralleling of outputs | Yes for redundancy, Yes for double current (maximum 2) |
| Output protection type | Transient voltage suppression per channel, Short circuit protection per channel, Overload/thermal protection per channel, Reverse polarity protection per module |
| Output diagnostic | Power supply error per channel, Over current error per channel |
| Power supply type | Bus power from power supply bus (24 Vdc), Field power from power supply field (24 Vdc) |
| Rated operational voltage limits | 20.4...28.8 V DC |
| Typical current consumption | 33.6 mA 24 V DC on the Bus current, 3.6 mA 24 V DC on the internal field current minimum, 4004.3 mA 24 V DC on the internal field current maximum |
| Electrical Connection | Screw/spring terminal block |
| Power dissipation in W | 1.83 W maximum at 24 V DC |
| Isolation between channels and bus | 1500 V AC |
| Isolation between channels and ground | 1500 V AC |
| Hot swapping fallback | Yes |
| Local signalling | 1 LED (green) for module operating (RUN), 1 LED per channel (green) for channel diagnostic, 1 LED (red) for module error (ERR) |
| Housing Colour | Grey |
| Mounting support | Top hat type TH35-7.5 rail IEC 60715, Top hat type TH35-15 rail IEC 60715 |
| Height | 4.8 in (121 mm) |
| Width | 0.6 in (15 mm) |
| Depth | 3.1 in (80 mm) |
| Net Weight | 0.172 lb(US) (0.078 kg) |
| IP Degree of Protection | IP20 |
|---|---|
| Marking | CE, UKCA, CULus, RCM |
| Product certifications | CE, UKCA, CULus, RCM, Merchant Navy - EU RO MR (pending), EAC (pending), ATEX Zone 2 (pending), IECEx zone 2 (pending), CCC Ex zone 2 (pending) |
| Standards | EN/IEC 61131-2, EN 61010-2-201, UL 61010-2-201, IACS E10, EN/IEC 61000-6-5, interface type 1 and type 2, EN/IEC 61850-3, location G, EN/IEC 60079-0, EN 50155, EN 50121-4, EN 50121-5 |
| Directives | 2014/30/EU - electromagnetic compatibility, 2014/34/EU - ATEX directive, 2014/35/EU |
| Ambient air temperature for operation | -4…140 °F (-20…60 °C) |
| Ambient air temperature for storage | -40…185 °F (-40…85 °C) |
| Relative humidity | 5…95 % without condensation |
| Operating altitude | 0...6561.68 ft (0...2000 m) without derating, 2000...5000 m with derating |
| Pollution degree | 2 |
| Environmental characteristic | Gas resistant C3 and G2 |
| Vibration resistance | 1 g without accessory, 2 g with accessory |
| Shock resistance | 15 g 11 ms with and without accessory) |
| Part number | NTSDDO0802XK |
|---|---|
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3606486877708 |
| Warranty (in months) | 18 |
|---|
| Country of origin | ID |
|---|---|
| Shipping weight | 0.078 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
No documents are on file for this part yet.
Ask us for the datasheetThe tariff (HS) code on file for NTSDDO0802XK is 853710.
The EAN (GTIN) of NTSDDO0802XK is 3606486877708.
NTSDDO0802XK ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.
PLC selection guide for engineers covering IEC 61131 compliance, Siemens, Rockwell, Schneider, ABB comparison, scan time sizing, and wiring. Shop at Stoklink.
Learn how a PLC works, including scan cycle, I/O sizing, IEC 61131-3 programming, and hardware selection for ABB, Schneider, and Siemens. Shop at Stoklink.
Master PLC system components: CPU, power supply, I/O modules, communication interfaces, and software with sizing formulas and selection tips. Shop at Stoklink.