Part number
METSEPM5560
Model no
PM5560
2,078.33 SR On request Dispatch — · From TürkiyeGet a Quote

Schneider Electric METSEPM5560 PowerLogic PM5560 Class 0.2S 63rd Harmonic 2 Ethernet 4DI 2DO Power Meter

PowerLogic PM5560 flush-mount power meter, Class 0.2S accuracy, 63rd harmonic, dual Ethernet, 4 DI, 2 DO, 52 alarms.

Rated current
1 A
Rated operational voltage
20–400 V AC
Communication
RS485 Modbus RTU/ASCII, 2x Ethernet Modbus TCP/IP, BACnet IP, DNP3
Display
Backlit LCD, 128 x 128 pixels
EAN
3606480614064
Description

About the PM5560

The Schneider Electric METSEPM5560 is a PowerLogic PM5560 flush-mount power meter with Class 0.2S accuracy to IEC 62053-22 and 128 samples per cycle. It measures voltage, current, frequency, power factor and active/reactive power, resolves harmonics to the 63rd order, and monitors neutral current directly with calculated ground current. Dual Ethernet ports carry Modbus TCP/IP, EtherNet/IP, BACnet/IP and DNP3, alongside an RS485 Modbus RTU/ASCII port.

Certifications & Standards

  • CE
  • cULus
  • BTL
  • EN 50470-1
  • EN 50470-3
  • IEC 60529
  • IEC 61557-12
  • IEC 62053-22
  • IEC 62053-23
  • IEC 62053-24
  • IEC 62052-11
  • IEC 62052-31
  • ANSI C12.20

Selection Notes

The PM5560 adds dual daisy-chainable Ethernet ports and 63rd-harmonic resolution over the RS485-only PM5350, so it fits switchboards where a web server, onboard diagnostics or a Modbus TCP/BACnet gateway is already planned. Direct neutral-current and calculated ground-current monitoring on all four digital inputs supports branch-level WAGES metering without extra CTs. Where waveform capture or residual-current monitoring is also required, the PM5650/PM5660/PM5760 variants in the same enclosure add those functions on top of this base feature set.

Specification

Full specification

63 values · Last verified 30 Oct 2026

Main 4

Range PowerLogic
Product name PowerLogic PM5000
Product or Component Type Power meter
Device short name PM5560

Complementary 38

Power quality analysis up to the 63rd harmonic
Metering type Measured neutral current, Calculated ground current
Device Application Gateway, WAGES metering, Power monitoring, Multi-tariff
Type of measurement Current, Voltage, Frequency, Power factor, Energy, Active and reactive power
[Us] rated supply voltage 100...300 V DC, 90...528 V AC 45...65 Hz
Network Frequency 60 Hz, 50 Hz
Line Rated Current 1 A, 5 A
type of network 3P + N, 3P, 1P + N
Maximum power consumption in VA 16 VA 480 V
Ride-through time 35 ms 120 V AC typical, 129 ms 230 V AC typical, 50 ms 125 V DC typical
Display Type Backlit LCD
Display Resolution 128 x 128 pixels
Sampling rate 128 samples/cycle
Measurement current 50…10000 mA
Analogue input type Voltage (impedance 5 MOhm), Current (impedance <= 0.3 mOhm)
Measurement voltage 20…400 V AC 45...65 Hz between phase and neutral, 20…828 V AC 45...65 Hz between phases
Frequency measurement range 45…65 Hz
Number of inputs 4 digital
Measurement accuracy Apparent power +/- 0.5 %, Frequency +/- 0.05 %, Active energy +/- 0.2 %, Reactive energy +/- 1 %, Active power +/- 0.2 %, Voltage +/- 0.1 %, Power factor +/- 0.005, Current +/- 0.15 %, Reactive power +/- 1 %
Accuracy class Class 0.2S active energy IEC 62053-22
Number of Outputs 2 digital
Information displayed Tariff 8)
Communication port protocol Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V, JBUS, Modbus TCP/IP 10/100 Mbit/s 2500 V, Ethernet Modbus TCP/IP daisy chain, BACnet IP, DNP3 over ethernet
Communication port support RS485, ETHERNET
Communication gateway Ethernet/serial
Data recording Event logs, Maintenance logs, Min/max of instantaneous values, Data logs, Alarm logs, Time stamping
Memory capacity 1.1 MB
Web services Alarm notification by e-mail, Diagnostic via predefined web pages, Web server, Real time viewing of data
Ethernet service SNTP client, SNMP-Traps
Connections - terminals Voltage circuit screw terminal block4, Control circuit screw terminal block2, Current transformer screw terminal block6, RS485 link screw terminal block4, Digital input screw terminal block8, Digital output screw terminal block4, Ethernet network RJ45 connector2
Mounting Mode Flush-mounted
Mounting support Framework
Standards EN 50470-3, IEC 61557-12:2015, IEC 62053-22:2020, IEC 62053-24, IEC 60529, EN 50470-1, UL 61010-1, ANSI C12.20, IEC 62053-23:2020, IEC 62052-11:2020, IEC 62052-31:2015
Product certifications CE conforming to IEC 61010-1, CULus conforming to UL 61010-1, BTL
Width 3.8 in (96 mm)
Depth 2.8 in (72 mm)
Height 3.8 in (96 mm)
Net Weight 15.9 oz (450 g)

Environment 7

Electromagnetic compatibility Limits for harmonic current emissions class A conforming to IEC 61000-3-2, Conducted RF disturbances level 3 conforming to IEC 61000-4-6, Magnetic field at power frequency level 4 conforming to IEC 61000-4-8, Conducted and radiated emissions class B conforming to EN 55022, Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3, Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2, Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3, Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4, Surge immunity test level 4 conforming to IEC 61000-4-5, Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
IP degree of protection IP54 display: conforming to IEC 60529, IP30 rear: conforming to IEC 60529
Relative humidity 5…95 % 122 °F (50 °C) non-condensing
Pollution degree 2
Ambient air temperature for operation -13…158 °F (-25…70 °C)
Ambient Air Temperature for Storage -40…185 °F (-40…85 °C)
Operating altitude <= 9842.52 ft (3000 m)
Show all 63 specifications ↓ Show less ↑14 more values in Identification, Contractual warranty, Logistics.

Identification 8

Part number METSEPM5560
Type designation PM5560
Brand Schneider Electric
Condition New, factory sealed
Source Schneider Electric and its authorised distributors
Warranty Manufacturer warranty
Lifecycle status Active, in production
EAN 3606480614064

Contractual warranty 1

Warranty (in months) 18

Logistics 5

Country of origin IN
Shipping weight 0.45 kg
Ships from Türkiye
Dispatch —
Stock On request

Source: manufacturer data · Last verified: 30 Oct 2026

Documents

Documents for METSEPM5560

No documents are on file for this part yet.

Ask us for the datasheet
Certifications

Certifications and standards

  • UL
  • CE
  • EN 50470-3
  • IEC 61557-12:2015
  • IEC 62053-22:2020
  • IEC 62053-24
  • IEC 60529
  • EN 50470-1
  • UL 61010-1
  • ANSI C12.20
  • IEC 62053-23:2020
  • IEC 62052-11:2020
  • IEC 62052-31:2015
Quick answers

Questions about the PM5560

What is the rated current of PM5560?

The rated current of PM5560 is 1 A.

Which supply voltage is PM5560 rated for?

The rated operational voltage of PM5560 is 20–400 V AC.

What is the HS code of PM5560 for customs?

The tariff (HS) code on file for PM5560 is 902830.

What is the EAN of PM5560?

The EAN (GTIN) of PM5560 is 3606480614064.

Where does PM5560 ship from, and how fast?

PM5560 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.

Reviews

Customer reviews

2,078.33 SR On request
Get a Quote
Quote

Get a Quote

PM5560

Genuine parts

Genuine, factory-sealed parts

Schneider Electric · METSEPM5560

Every part on Stoklink is new, unused and made by the manufacturer named on the page.

Condition
New and unused, in the manufacturer's factory-sealed packaging.
Sourced from
Schneider Electric and its authorised distributors.
Warranty
The manufacturer's warranty applies.
If a part is not genuine
We refund the full amount.

Added to cart Could not add to cart

View cart