- Part number
- METSEPM5560
- Model no
- PM5560
Description
About the PM5560
About the PM5560
The Schneider Electric METSEPM5560 is a PowerLogic PM5560 flush-mount power meter with Class 0.2S accuracy to IEC 62053-22 and 128 samples per cycle. It measures voltage, current, frequency, power factor and active/reactive power, resolves harmonics to the 63rd order, and monitors neutral current directly with calculated ground current. Dual Ethernet ports carry Modbus TCP/IP, EtherNet/IP, BACnet/IP and DNP3, alongside an RS485 Modbus RTU/ASCII port.
Certifications & Standards
- CE
- cULus
- BTL
- EN 50470-1
- EN 50470-3
- IEC 60529
- IEC 61557-12
- IEC 62053-22
- IEC 62053-23
- IEC 62053-24
- IEC 62052-11
- IEC 62052-31
- ANSI C12.20
Selection Notes
The PM5560 adds dual daisy-chainable Ethernet ports and 63rd-harmonic resolution over the RS485-only PM5350, so it fits switchboards where a web server, onboard diagnostics or a Modbus TCP/BACnet gateway is already planned. Direct neutral-current and calculated ground-current monitoring on all four digital inputs supports branch-level WAGES metering without extra CTs. Where waveform capture or residual-current monitoring is also required, the PM5650/PM5660/PM5760 variants in the same enclosure add those functions on top of this base feature set.
Specification
Full specification
Main 4
| Range | PowerLogic |
|---|---|
| Product name | PowerLogic PM5000 |
| Product or Component Type | Power meter |
| Device short name | PM5560 |
Complementary 38
| Power quality analysis | up to the 63rd harmonic |
|---|---|
| Metering type | Measured neutral current, Calculated ground current |
| Device Application | Gateway, WAGES metering, Power monitoring, Multi-tariff |
| Type of measurement | Current, Voltage, Frequency, Power factor, Energy, Active and reactive power |
| [Us] rated supply voltage | 100...300 V DC, 90...528 V AC 45...65 Hz |
| Network Frequency | 60 Hz, 50 Hz |
| Line Rated Current | 1 A, 5 A |
| type of network | 3P + N, 3P, 1P + N |
| Maximum power consumption in VA | 16 VA 480 V |
| Ride-through time | 35 ms 120 V AC typical, 129 ms 230 V AC typical, 50 ms 125 V DC typical |
| Display Type | Backlit LCD |
| Display Resolution | 128 x 128 pixels |
| Sampling rate | 128 samples/cycle |
| Measurement current | 50…10000 mA |
| Analogue input type | Voltage (impedance 5 MOhm), Current (impedance <= 0.3 mOhm) |
| Measurement voltage | 20…400 V AC 45...65 Hz between phase and neutral, 20…828 V AC 45...65 Hz between phases |
| Frequency measurement range | 45…65 Hz |
| Number of inputs | 4 digital |
| Measurement accuracy | Apparent power +/- 0.5 %, Frequency +/- 0.05 %, Active energy +/- 0.2 %, Reactive energy +/- 1 %, Active power +/- 0.2 %, Voltage +/- 0.1 %, Power factor +/- 0.005, Current +/- 0.15 %, Reactive power +/- 1 % |
| Accuracy class | Class 0.2S active energy IEC 62053-22 |
| Number of Outputs | 2 digital |
| Information displayed | Tariff 8) |
| Communication port protocol | Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V, JBUS, Modbus TCP/IP 10/100 Mbit/s 2500 V, Ethernet Modbus TCP/IP daisy chain, BACnet IP, DNP3 over ethernet |
| Communication port support | RS485, ETHERNET |
| Communication gateway | Ethernet/serial |
| Data recording | Event logs, Maintenance logs, Min/max of instantaneous values, Data logs, Alarm logs, Time stamping |
| Memory capacity | 1.1 MB |
| Web services | Alarm notification by e-mail, Diagnostic via predefined web pages, Web server, Real time viewing of data |
| Ethernet service | SNTP client, SNMP-Traps |
| Connections - terminals | Voltage circuit screw terminal block4, Control circuit screw terminal block2, Current transformer screw terminal block6, RS485 link screw terminal block4, Digital input screw terminal block8, Digital output screw terminal block4, Ethernet network RJ45 connector2 |
| Mounting Mode | Flush-mounted |
| Mounting support | Framework |
| Standards | EN 50470-3, IEC 61557-12:2015, IEC 62053-22:2020, IEC 62053-24, IEC 60529, EN 50470-1, UL 61010-1, ANSI C12.20, IEC 62053-23:2020, IEC 62052-11:2020, IEC 62052-31:2015 |
| Product certifications | CE conforming to IEC 61010-1, CULus conforming to UL 61010-1, BTL |
| Width | 3.8 in (96 mm) |
| Depth | 2.8 in (72 mm) |
| Height | 3.8 in (96 mm) |
| Net Weight | 15.9 oz (450 g) |
Environment 7
| Electromagnetic compatibility | Limits for harmonic current emissions class A conforming to IEC 61000-3-2, Conducted RF disturbances level 3 conforming to IEC 61000-4-6, Magnetic field at power frequency level 4 conforming to IEC 61000-4-8, Conducted and radiated emissions class B conforming to EN 55022, Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3, Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2, Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3, Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4, Surge immunity test level 4 conforming to IEC 61000-4-5, Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
|---|---|
| IP degree of protection | IP54 display: conforming to IEC 60529, IP30 rear: conforming to IEC 60529 |
| Relative humidity | 5…95 % 122 °F (50 °C) non-condensing |
| Pollution degree | 2 |
| Ambient air temperature for operation | -13…158 °F (-25…70 °C) |
| Ambient Air Temperature for Storage | -40…185 °F (-40…85 °C) |
| Operating altitude | <= 9842.52 ft (3000 m) |
Show all 63 specifications ↓ Show less ↑14 more values in Identification, Contractual warranty, Logistics.
Identification 8
| Part number | METSEPM5560 |
|---|---|
| Type designation | PM5560 |
| Brand | Schneider Electric |
| Condition | New, factory sealed |
| Source | Schneider Electric and its authorised distributors |
| Warranty | Manufacturer warranty |
| Lifecycle status | Active, in production |
| EAN | 3606480614064 |
Contractual warranty 1
| Warranty (in months) | 18 |
|---|
Logistics 5
| Country of origin | IN |
|---|---|
| Shipping weight | 0.45 kg |
| Ships from | Türkiye |
| Dispatch | — |
| Stock | On request |
Source: manufacturer data · Last verified: 30 Oct 2026
Documents
Documents for METSEPM5560
No documents are on file for this part yet.
Ask us for the datasheet
Certifications
Certifications and standards
- UL
- CE
- EN 50470-3
- IEC 61557-12:2015
- IEC 62053-22:2020
- IEC 62053-24
- IEC 60529
- EN 50470-1
- UL 61010-1
- ANSI C12.20
- IEC 62053-23:2020
- IEC 62052-11:2020
- IEC 62052-31:2015
Quick answers
Questions about the PM5560
What is the rated current of PM5560?
The rated current of PM5560 is 1 A.
Which supply voltage is PM5560 rated for?
The rated operational voltage of PM5560 is 20–400 V AC.
What is the HS code of PM5560 for customs?
The tariff (HS) code on file for PM5560 is 902830.
What is the EAN of PM5560?
The EAN (GTIN) of PM5560 is 3606480614064.
Where does PM5560 ship from, and how fast?
PM5560 ships from Türkiye. Shipping calculated at checkout · import duties and taxes paid on arrival.